3RB2016-1SB0 SIEMENS, 3RB2016-1SB0 Datasheet - Page 17

RELAY, OVERLOAD, 3-12A

3RB2016-1SB0

Manufacturer Part Number
3RB2016-1SB0
Description
RELAY, OVERLOAD, 3-12A
Manufacturer
SIEMENS
Datasheet

Specifications of 3RB2016-1SB0

Control Voltage Range
690V
Load Current
12A
Control Voltage Ac Max
690VAC
External Depth
73mm
External Length / Height
64mm
External Width
45mm
Operating Frequency Max
60Hz
Operating Frequency Min
50Hz
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3RB22/3RB23 solid-state overload relays for full motor protection with screw terminals or spring-loaded terminals
for stand-alone installation, CLASS 5, 10, 20 and 30 adjustable
Features and technical specifications:
• Overload protection, phase failure protection and unbalance
• External power supply 24 ... 240 V AC/DC
• Auxiliary contacts 2 NO +2 NC
• Manual and automatic RESET
• Electrical remote RESET integrated
• 4 LEDs for operating and status displays
1)
* You can order this quantity or a multiple thereof.
3RB2. 83-4AA1
3RB2. 83-4AC1
Evaluation modules
Evaluation modules
Function expansion modules
protection
The analog signal DC 4 ... 20 mA can be used for operating rotary coil
instruments or for feeding into analog inputs of programmable logic
controllers.
Size of
contactor
S00 ... S12
Size of
contactor
S00 ... S12
Size of
contactor
S00 ... S12
Version
Monostable
Bistable
Version
Monostable
Bistable
Version
for plugging into evaluation module (1 unit)
Analog Basic 1
Analog output DC 4 ... 20 mA,
with overload warning
Analog Basic 1 GF
Analog output DC 4 ... 20 mA,
with internal ground fault detection and
overload warning
Analog Basic 2 GF
Analog output DC 4 ... 20 mA,
with internal ground fault detection and
ground fault signaling
Basic 1 GF
with internal ground fault detection and
overload warning
Basic 2 GF
with internal ground fault detection and
ground fault signaling
2)
2)
modules
modules
1)
modules
1)2)
1)2)
modules
modules
© Siemens AG 2007
• TEST function and self-monitoring
• Internal ground fault detection with function expansion
• Screw terminals or spring-loaded terminals for auxiliary,
• Input for PTC sensor circuit
• Analog output with function expansion module
2)
DT Screw terminals
}
}
DT Spring-loaded terminals
A
A
DT Order No.
}
}
}
}
}
module
control and sensor circuits
The following information on ground-fault protection refers to sinusoidal
residual currents at 50/60 Hz:
- With a motor current of between 0.3 and 2 times the set current
- With a motor current of between 2 and 8 times the set current
- The response delay amounts to between 0.5 and 1 second.
will trip at a ground-fault current equal to 30 % of the set current.
will trip at a ground fault-current equal to 15 % of the set current.
Order No.
3RB22 83-4AA1
3RB23 83-4AA1
Order No.
3RB22 83-4AC1
3RB23 83-4AC1
3RB29 85-2AA0
3RB29 85-2AA1
3RB29 85-2AB1
3RB29 85-2CA1
3RB29 85-2CB1
3RB22, 3RB23 for high-feature applications
3RB2 Solid-State Overload Relays
Price
per PU
Price
per PU
Price
per PU
Overload Relays
PU
(UNIT,
SET, M)
PU
(UNIT,
SET, M)
PU
(UNIT,
SET, M)
Siemens LV 1 · 2007
1
1
1
1
1
1
1
1
1
PS*
PS*
PS*
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
1 unit
PG
PG
PG
101
101
101
101
101
101
101
101
101
I
I
e
Weight
per PU
approx.
kg
Weight
per PU
approx.
kg
Weight
per PU
approx.
kg
e
the unit
5/47
the unit
0.300
0.300
0.300
0.300
0.030
0.030
0.030
0.030
0.030

Related parts for 3RB2016-1SB0