GN350ASR Crouzet USA, GN350ASR Datasheet

SSR, PANEL MOUNT, 530VAC, 260VAC, 50A

GN350ASR

Manufacturer Part Number
GN350ASR
Description
SSR, PANEL MOUNT, 530VAC, 260VAC, 50A
Manufacturer
Crouzet USA
Datasheet

Specifications of GN350ASR

Control Voltage Range
180VAC To 260VAC
Operating Voltage Range
48VAC To 530VAC
Load Current
50A
Isolation Voltage
4000Vrms
Control Voltage Type
AC
Output Current
50A
Output Device
SCR
Output Voltage Min
48VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Output Specifications
Output Current (40°C)
Voltage range (Vrms) (1)
Peak Voltage (Vpk , t = I min.)
Off-state leakage mArms
(without RC / with RC)
Minimum Current (mArms)
1 cycle surge current 50-60 Hz
(Apk, Ta = 25ºC)
1 second surge current 50/60 Hz
(Apk, Ta = 25ºC)
Forward voltage drop
(Vpk @ Imax, Ta = 40ºC)
I
Rjb (thermal res. Junction to
baseplate, °C/W)
Static off-state dv/dt
(Vµs, Ta = 25ºC)
HP Ratings at 240V
HP Ratings at 480V
HP Ratings at 600V
Min/Max wire size
Torque (N-m)
Input Specifications
Input voltage
Drop out voltage
Min. input current (for on-state)
Maximum input current
Input Resistance (Ohms)
Turn-on time (2)
Turn-off time
Min/Max stranded/solid wire
Torque (N-m)
General Characteristics
Operating Temperature (ºC)
Storage Temperature (ºC)
Input to output isolation
Input/output to ground isolation
Input to output capacitance
Operating Frequency
Housing Material
Weight (grams)
Standards of Compliance
CE Compliant with the LVD 73/23/EEC
UL Recognized per UL 508 and CSA C22.2 no. 14-95
TUV Certified per EN 60950
IEC 62314
IEC 60068-2-6
IEC 60068-2-27
IEC 61000-4-2 Level 3
IEC 61000-4-3 Level 3
IEC 61000-4-4 Level 3
IEC 61000-4-5 Level 3
IEC 61000-4-6 Level 3
CISPR 11 Class A
GN3 Series 3 Phase Solid State Relay - DC Input
2
T (50-60Hz, ½ cycle)
Three-phase solid-state relay
Ratings up to 50 amps @ 530Vac
DBC substrate for superior thermal performance
Epoxy-free design reduces internal com
Back-to-Back dual SCR output for heavy industrial loads
100k-cycle UL508 endurance rating for enhanced reliability
No external transient protection required (internal TVS)
EMC Compliant for reliable operation in harsh environments
UL/CSA/TUV Approved, CE & RoHS Compliant
35mm/10-55Hz
15G / 11ms
Electrostatic Discharge
Radiated Electromagnetic Noise
Immunity to Electrically Fast Transients
Immunity to Electrical Surges
Conducted Electromagnetic Noise
Conducted and Radiated Noise for Industrial Enviroments
Order/Technical Support - Tel: (877) 502-5500 / Fax: (619) 710-8540 / www.crouzet-usa.com
48-600Vac
16/8 AWG
0.06 / 3.0
275-300
380-370
1100
1.35
0.24
100
500
25
85
3
1
5
Products and specifications subject to change without notice
Current Regulated
-40 to + 80
-40 to + 100
2500Vrms
4000Vrms
8pF (typical)
47 to 63 Hz
UL 94V0 (self extinguishing)
24/14 AWG
8.33msec
8.33msec
4-32Vdc
24mA
35mA
360
1Vdc
2.4
1.9
48-600Vac
2520-2320
16/8 AWG
0.06 / 3.0
710-750
1100
1.35
0.12
100
150
500
7.5
50
10
3
Notes:
(1) Voltage range for relay with snubber circuit is 48-530Vac.
(2) Random SSR's turn on in less than 100µs
Part Numbers
Part Numbers
Part Numbers
Part Numbers
25 Amp
50 Amp
25 Amp
50 Amp
25 Amp
50 Amp
25 Amp
50 Amp
Rating
Rating
Rating
Rating
48-600Vac
48-600Vac
48-600Vac
48-600Vac
48-530Vac
48-530Vac
48-530Vac
48-530Vac
Zero Crossing Output
Zero Crossing Output
Random Fire Output
Random Fire Output
Output
Output
Output
Output
4-32Vdc
4-32Vdc
4-32Vdc
4-32Vdc
4-32Vdc
4-32Vdc
4-32Vdc
4-32Vdc
Input
Input
Input
Input
Part Number
Part Number
Part Number
Part Number
GN325DLR
GN350DLR
GN325DSZ
GN350DSZ
GN325DSR
GN350DSR
GN325DLZ
GN350DLZ

Related parts for GN350ASR

GN350ASR Summary of contents

Page 1

GN3 Series 3 Phase Solid State Relay - DC Input Three-phase solid-state relay Ratings amps @ 530Vac DBC substrate for superior thermal performance Epoxy-free design reduces internal com Back-to-Back dual SCR output for heavy industrial loads 100k-cycle ...

Page 2

... GN325ASR 25 Amp 48-530Vac 90-140VAC 25 Amp 48-530Vac 18-36Vac 50 Amp 48-530Vac 180-260VAC GN350ASR 50 Amp 48-530Vac 90-140VAC 50 Amp 48-530Vac 18-36Vac Notes: (1) Voltage range for relay with snubber circuit is 48-530Vac. (2) Random AC input SSR's turn-on is 20mS (3) Operatinting temperature for 180-260VAC input is -20 to +60°C ...

Page 3

Dimensional Drawings For GN3 Dimensions mm (inches) AC Input Equivalent Circuit no Snubber Order/Technical Support - Tel: (877) 502-5500 / Fax: (619) 710-8540 / www.crouzet-usa.com DC Input Equivalent Circuit no Snubber Products and specifications subject to change without notice ...

Page 4

GN3 SSR Derate Curves DERATE CURVES: GN3 3 Phase SSR 25A Ambient Temperature (°C) AC Input Equivalent Circuit with Snubber Order/Technical Support - Tel: (877) 502-5500 / Fax: (619) ...