BR1E IDEC, BR1E Datasheet - Page 65

no-image

BR1E

Manufacturer Part Number
BR1E
Description
CONTACT BLOCK, 2NO, 10A, SCREW
Manufacturer
IDEC
Datasheet

Specifications of BR1E

No. Of Poles
2
Contact Current Max
10A
Contact Voltage Ac Max
600V
Contact Voltage Dc Max
220V
Switch Terminals
Screw
For Use With
ARN/ARNS Series Mono-lever Switches
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Installation of LED Illuminated Units
1. Note the polarity for wiring when connecting to DC-DC
2. Transformer type units are recommended for use in areas
Notes on LED Illuminated Units
LED lamps consist of semiconductors. If the applied voltage
exceeds the rated voltage, LED elements may deteriorate
due to overheat, resulting in significant decrease in lumi-
nance, hue change, or failure of lighting. Also, if an extrane-
ous noise, transient voltage, or transient current is applied to
the circuit, similar effects may occur. When using LED
lamps, observe the following instructions.
The LED lamps are rated at 6V, 12V, or 24V AC/DC, and can
be used within ±10% the rated voltage of either AC or DC.
1. Switching power supply
2. Rechargeable battery
3. Full-wave rectification
4. Single-phase half-wave rectification
LED elements deteriorate due to extraneous noise, resulting
in significant decrease in luminance, hue change, or failure
of lighting. When such effects are anticipated, take a protec-
tion measure shown below, such as RC elements or a surge
absorber.
Rated Voltage
DC Power
Noise
converter unit.
subjected to noise.
Regulated voltage from switching power supply is best
suited. Make sure to use within the rated voltage of the
LED lamp.
Note that the battery voltage may exceed the rated volt-
age of the LED lamp while the battery is being charged
and immediately after the charging is complete. Be sure
to use the LED lamp on a voltage of ±10% the rated volt-
age.
Since the LED lamp is AC/DC compatible, a diode bridge
for rectification is not necessary. If the LED lamp is used
on a full-wave rectification current through a diode bridge,
the rectifier diodes will reduce the voltage, resulting in
lower luminance.
This is not suitable for the power source of LED lamps.
Use constant-voltage DC power.
Terminal No.
X1
X2
Negative
Positive
Polarity
3. Notes for Pure White LED Lamps
[Protection Example 1] For AC circuit
[Protection Example 2] For DC circuit
1. Leakage currents through the transistors or a contact
2. When the LED lamp is illuminated by a transistor output,
[Circuit Example]
Connect shunt resistor R in parallel with the LED lamp.
Do not use the pure white LED outdoors, otherwise it will
lead to the degradation of brightness and color. Do not
remove or apply shock to the cap on the pure white LED
lamp, otherwise it may break or damage the cap.
For the pure white LED, use a white lens. The illumination
color will be dull if a different color is used.
+
Countermeasures against Dim Lighting
protection circuit may cause the LED lamp to illuminate
dimly even when the output is off.
take the following measure.
transformer
LED with
Relay
coil or
solenoid
ø30
Ry
LED
LED
Series
C
R
Io: Leakage current when the output is off
R: Shunt resistor
Diode
Instructions
(Reference values of the diode)
Forward current: More than the Ry coil current
Reverse withstand voltage: Ry coil current
(Reference values) R: 120
Relay
coil or
solenoid
Ry
Io
LED
R
C: 0.1 F
LED with
transformer
LED
C
R
ø30
65
10

Related parts for BR1E