240D10-17 OPTO 22, 240D10-17 Datasheet - Page 11

SSR, 10A, 240VAC

240D10-17

Manufacturer Part Number
240D10-17
Description
SSR, 10A, 240VAC
Manufacturer
OPTO 22
Datasheets

Specifications of 240D10-17

Control Voltage Range
3Vdc To 32Vdc
Operating Voltage Range
24VAC To 280VAC
Load Current
10A
Isolation Voltage
4000V
Control Voltage Type
DC
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
UL, CSA
Control Voltage
RoHS Compliant
Brand/series
DC Series
Current, Rating
10 A
Function
Timing
Mounting Type
PCB
Relay Type
Solid State
Termination
Screw
Timer Type
Off Delay
Voltage, Control
240 VAC
Relay Terminals
Screw
Rohs Compliant
Yes
Lead Free Status / Rohs Status
RoHS Compliant part
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909)695-3000 • (800)321-OPTO • Fax: (909)695-3095 • Internet: www.opto22.com
Inside Sales: (800)452-OPTO • Product Support: (800)TEK-OPTO • (909)695-3080 • Fax: (909)695-3017 • E-mail: support@opto22.com • FaxBack: (800)474-OPTO
DATA SHEET
Solid-State Relays In Series
In applications requiring greater current rating at higher voltage,
two Opto 22 SSRs may be operated in series for double the
voltage rating. The built-in snubber in each SSR assures proper
voltage sharing of the two SSRs in series. In the diagram below,
two 240-volt, 45-amp SSRs are connected in series for operation
on a 480-volt line. The control is shown with a parallel hook-up
but it should be noted that a serial connection can also be
implemented.
Form 859-990514
Applications
Lamp Loads
Since all Opto 22 SSRs are zero voltage switching, they
are ideal for driving incandescent lamps because the
initial inrush current into a cold filament is reduced.
The life of the lamp is increased when switched by a
zero voltage turn on SSR. The following table is a guide
to selecting an Opto 22 SSR for switching a given
incandescent lamp.
Tips (Continued)
SSR CURRENT RATING
SSR CURRENT RATING
45-Amp
45-Amp
10-Amp
25-Amp
10-Amp
25-Amp
2-Amp
4-Amp
2-Amp
4-Amp
120 Volt Lamps
240 Volt Rating
LAMP RATING
LAMP RATING
4 Kilowatt
1 Kilowatt
2 Kilowatt
3 Kilowatt
2 Kilowatt
6 Kilowatt
400 Watt
100 Watt
200 Watt
800 Watt
SOLID-STATE RELAYS
Heater Loads
Care should be taken in selecting a SSR for driving a heater load if
the load is cycled on and off in a continuous manner as might occur in
a temperature control application. Constant cycling can cause thermal
fatigue in the thyristor chip at the point where the chip bonds to the
lead frame. Opto 22 employs a thick copper lead frame for mounting
the SCR chips in the power series SSRs to eliminate thermal fatigue
failures. In addition, Opto 22 recommends operating any SSR at 75%
rated current for cycling heater loads to ensure complete reliability.
The following table is a guide to selecting the proper SSR for a given
heater load.
Current Rating
Nominal SSR
10 480V
10 480V
45-Amp
10-Amp
25-Amp
2-Amp
4-Amp
Recommended
Heater Current
Maximum
1½-Amp
2½-Amp
7½-Amp
18-Amp
35-Amp
8-Amp
8-Amp
page 11/12