750134 PILZ, 750134 Datasheet - Page 6
![no-image](/images/no-image-200.jpg)
750134
Manufacturer Part Number
750134
Description
PNOZ S4 24-240 VAC
Manufacturer
PILZ
Datasheet
1.750134.pdf
(10 pages)
Specifications of 750134
Coil Voltage Vac Nom
240V
Contact Current Max
6A
Contact Voltage Ac Nom
240V
Contact Voltage Dc Nom
24V
No. Of Poles
3
Relay Mounting
DIN Rail
External Width
22.5mm
External Depth
120mm
Svhc
No SVHC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s4
Installation
Install base unit without contact ex-
pander module:
Connect base unit and PNOZsigma
contact expander module:
Installation in control cabinet
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Ensure that the plug terminator is
inserted at the side of the unit.
Remove the plug terminator at the
side of the base unit and at the con-
tact expander module.
Connect the base unit and the con-
tact expander module to the sup-
plied connector before mounting
the units to the DIN rail.
The safety relay should be installed
in a control cabinet with a protec-
tion type of at least IP54.
Use the notch on the rear of the unit
to attach it to a DIN rail.
Ensure the unit is mounted securely
on a vertical DIN rail (35 mm) by us-
ing a fixing element (e.g. retaining
bracket or an end angle).
Push the unit upwards or down-
wards before lifting it from the DIN
rail.
Terminal configuration
Dimensions
*with spring-loaded terminals