253-TAAU-LSFA-C6 Tyco Electronics, 253-TAAU-LSFA-C6 Datasheet

Current Transducer

253-TAAU-LSFA-C6

Manufacturer Part Number
253-TAAU-LSFA-C6
Description
Current Transducer
Manufacturer
Tyco Electronics
Datasheet

Specifications of 253-TAAU-LSFA-C6

Current Measuring Range Ac
1A To 10A
Sensor Output
Current
Frequency Max
60Hz
Frequency Min
50Hz
Transducer Input Current Ac Max
5A
Output Current Max
1mA
Current Range Ac
1-10A
Accuracy
0.5%
Lead Free Status / RoHS Status
na
Paladin Transducers 250 Series Class 0.5
Features
Extensive range
High accuracy 0.5%
Up to 3 analogue outputs in one
housing
Zero and span adjustments
DIN rail mounting
Single and 3 phase systems
Flame retardant cases
Screw clamp terminals
Benefits
Cost saving remote metering
Reduction of signal levels for ease of
metering
Isolated output for safety
Protection against high voltage and
overload
Applications
Switchgear
Distribution systems
Generator sets
Control panels
Energy management
Building management
Utility power monitoring
Process control
Motor control
Approvals
UL File No: E140758
CSA File No: LR52592
BV File No: 3896H-07425-AO PRSO BV
An extensive range of Class 0.5 transducers providing measurement, isolation
and conversion of electrical parameters into industry standard DC output signals.
The range offers protection against high voltage and overload, and resistance
to vibration in harsh electrical environments. Transducers offer multiple
analogue outputs from one housing, and individual measurement of most
electrical parameters.
Introduction
Crompton transducers can be used for measuring most electrical parameters.
The following transducers can be supplied:
• A.C. and D.C. current and voltage.
• Active, reactive and apparent power.
• Frequency.
• Power Factor and Phase Angle.
• Integrating current for maximum demand indication and Alarm Control.
• Suppressed zero voltage for monitoring a narrow voltage range.
• Tap position on a high voltage transformer.
• Temperature transmitters for thermocouples and resistance thermometer
• Resistance (slidewire) transmitters.
Safety Features
Crompton transducers and transmitters are designed for use in harsh electrical
environments and feature:
• High protection against overload - 20 x rated current for 1 second.
• High degree of mechanical shock and vibration resistance.
• Protection against high voltage.
Application
• Measurement of most electrical parameters.
• Conversion to standard d.c. output signals.
• Outputs suitable for indication, PLC’s.
• For use in Control Cabinets, Switchboards, Motor Control Centres, Generating
Ordering Information
When ordering please specify:
1. Product catalogue number.
2 Current and/or voltage.
3. Frequency.
4. Auxiliary voltage A.C. or D.C.
5. Options e.g. calibration at 30°C.
6. For power products:
7. For slide wire transmitters quote R1, R2 and R3, see page G9.
8. National Specification:
detectors (RTD’s).
Inputs, outputs and power supply are galvanically isolated from one another
(excluding Resistance transmitters).
Sets, Energy Management & Building Management systems.
a. V.T. & C.T. ratios.
b. System configuration i.e. Single Phase, 3 Phase 3 or 4 Wire, balanced or
Indicated by 7th letter of part number.
unbalanced load.
9

Related parts for 253-TAAU-LSFA-C6

253-TAAU-LSFA-C6 Summary of contents

Page 1

... Safety Features Crompton transducers and transmitters are designed for use in harsh electrical environments and feature: • High protection against overload - 20 x rated current for 1 second. • High degree of mechanical shock and vibration resistance. • Protection against high voltage. Inputs, outputs and power supply are galvanically isolated from one another (excluding Resistance transmitters) ...

Page 2

... Paladin Transducers 250 Series Class 0.5 Specification Performance Designed to comply with BS6253 part 1, EN60688, IEC688, AS1384 and ANSI. C37. Temperature Range: Storage -20°C to +70°C Operating 0°C to +60°C Calibrated at 23°C Temperature Coefficient: 0.03%/ per °C Humidity Range 95% RH Zero Adjustment: ± ...

Page 3

... Product Code – 3 Phase Current Transducers - 3 D.C. Outputs Input A.C. A.C. Aux Power O/P D. 120V 0/1mA 120V 4/20mA With multiple analogue outputs, do not common the -ve terminals. 11 Catalogue No. Connection Diag. 253-TAA*-LSFA-C6 1 Catalogue No. Connection Diag. 256-TAA-LSFA-C6 47 Catalogue No. Connection Diag. 253-TAL*-LSHG-C6-DG 6 Catalogue No. Connection Diag. 256-TAS*-LSFA-C6-DG 2 256-TAL*-LSHG-C6-DG 2 ...

Page 4

... Time Constant O/P D.C. 1mA 8 Minutes 0/1mA 1mA 15 Minutes 0/1mA 1mA 30 Minutes 0/1mA 12 Catalogue No. Connection Diag. 253-TAR*-LSFA-C6-DG 6 Catalogue No. Connection Diag. 256-TAR*-LSFA-C6-DG 2 Catalogue No. Connection Diag. 253-TAP*-LSFA-C6-DG 8 253-TAN*-LSFA-C6-DG 8 253-TAM*-LSFA-C6-DG 8 Catalogue No. Connection Diag. 253-TDP*-FAFA-DG 4 253-TDN*-FAFA-DG 4 253-TDM*-FAFA-DG 4 ...

Page 5

... Auxiliary Power: Self Powered Outputs: 0/1mA, 0/5mA, 0/10mA and 0/20mA Product Code – Single Phase, Self Powered, 1 D.C. Output Input A.C. Aux Power O/P D.C. 120V 60Hz Self 0/1mA 13 Catalogue No. Connection Diag. 256-TAB*-LSM1-C6-PQ-T3 3 Catalogue No. Connection Diag. 253-TVA*-PQFA-C6 10 ...

Page 6

... Product Code – Single Phase - Suppressed Zero - A.C. Voltage Transducer, Self Powered - 1 D.C. Output Input A.C. A.C.Aux Power O/P D.C. 108 - 132V Self 0/1mA 14 Catalogue No. Connection Diag. 253-TVL*-PQHG-C6-DG 15 Catalogue No. Connection Diag. 256-TVL*-PQHG-C6-DG 11 256-TVS*-PQFA-C6-DG 11 Catalogue No. Connection Diag. 253-TVZ*-A9FA-C6 15 ...

Page 7

... D.C. Output Input A.C. Frequency O/P D.C. 120V 45/55Hz 0/1mA 120V 55/65Hz 0/1mA 120V 45/65Hz 0/1mA 120V 360/440Hz 0/1mA 15 Catalogue No. Connection Diag. 253-TVR*-PQFA-C6-DG 15 Catalogue No. Connection Diag. 256-TVR*-PQFA-C6-DG 11 Catalogue No. Connection Diag. 253-THZ*-PQFA-AG 10 253-THZ*-PQFA-AN 10 253-THZ*-PQFA-AJ 10 253-THZ*-PQFA-BI 10 ...

Page 8

... Product Code – Side Wire Transmitter (3 wire), Auxiliary Powered Input A.C. Aux Power O/P D.C. (Specify) R1, R2, R3 120V 0/1mA 16 Catalogue No. Connection Diag. 253-TRT*-TIFA-DG 12 253-TRT*-T5FA-DG 12 Catalogue No. Connection Diag. 253-TRP*-TRFA-DG 12 ...

Page 9

... I out x R Load limited to 15V Input Voltage: Typically I x (load + 200Ω) limited to 18V UL File Number: E149713N CSA File Number: LR52592 Product Code – Signal Isolator Input D.C. O/P D.C. 20mA 0/20mA 17 Catalogue No. Connection Diag. 253-TIK*-FAPO-DG 13 Catalogue No. Connection Diag. 250-ISA*-HF 5 ...

Page 10

... Copper: 2Ω minimum span, 20Ω maximum span Nickel: 20Ω minimum span, 200Ω maximum span 18 Catalogue No. Connection Diag. 256-TTA*-**FA-DG 18 256-TTM*-**FA-DG 18 256-TTV*-**FA-DG 18 256-TTN*-KTFA-DG 18 256-TTC*-TTFA-DG 18 256-TTF*-JTFA-DG 18 Catalogue No. Connection Diag. 253-TRR*-R1FA-DG 17 253-TRR*-R2FA-DG 17 ...

Page 11

... Square wave pulses from a multi-vibrator circuit with a mark-space ratio varied by the measured voltage, and amplitude varied by the measured current, are fed to an integrator and an output amplifier circuit. The D.C. milliamp signal produced is therefore directly proportional to the power input ...

Page 12

Paladin Transducers 250 Series Class 0.5 Power Factor and Phase Angle A range of power factor and phase angle transducers with a linearised output. Product Codes – Power Factor Transducer (for Digital Meters & Systems) 3 Phase ...