HAL 50-S LEM, HAL 50-S Datasheet - Page 2

Current Transducer

HAL 50-S

Manufacturer Part Number
HAL 50-S
Description
Current Transducer
Manufacturer
LEM
Datasheet

Specifications of HAL 50-S

Current Measuring Range Ac
± 150A
Current Measuring Range Dc
± 150A
Sensor Output
Voltage
Length/height, External
41mm
Frequency Max
50kHz
External Width
41.27mm
Accuracy
± 1%
Response Time
3µs
External Depth
28mm
Rohs Compliant
Yes
Accuracy %
1%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
061114/3
Dimensions HAL 50..600-S (in mm. 1 mm = 0.0394 inch)
Mechanical characteristics
Remarks
General tolerance
Primary through-hole
Connection of secondary
V
Temperature of the primary conductor should not exceed
90°C.
This is a standard model. For different versions please
contact us.
Bottom view
Front view
OUT
is positive when I
4.52
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
P
flows in the direction of the arrow.
32.23
± 0.5 mm
20 mm x 15 mm
Molex 5045-04-A
3
Ø4.5
Safety
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Secondary terminals
Terminal 1
Terminal 2
Terminal 3
Terminal 4
: supply voltage + 15 V
: supply voltage - 15 V
: output
: 0V
Left view
www.lem.com
Page 2/2