ACF-3000DM-A Amprobe, ACF-3000DM-A Datasheet

Current Transducer

ACF-3000DM-A

Manufacturer Part Number
ACF-3000DM-A
Description
Current Transducer
Manufacturer
Amprobe
Datasheets

Specifications of ACF-3000DM-A

Current Measuring Range Ac
300A To 3000A
Accuracy
± 1%
Accuracy %
1%
Rohs Compliant
NA
For Use With
DM-II And DMII Pro
Lead Free Status / RoHS Status
na
P/N 964774 rev.A
OPERATING INSTRUCTIONS
for
AMPROBE
®
Flexible Current Transducer
Model ACF-3000DM-A
AMPROBE
1

Related parts for ACF-3000DM-A

ACF-3000DM-A Summary of contents

Page 1

... OPERATING INSTRUCTIONS for AMPROBE ® Flexible Current Transducer Model ACF-3000DM-A AMPROBE 1 P/N 964774 rev.A ...

Page 2

... TABLE OF CONTENTS LIMITED WARRANTY ..................................................................................3 INTRODUCTION ..........................................................................................4 ACF-3000DM-A ELECTRONICS PACKAGE................................................4 FLEXIBLE AC CURRENT TRANSDUCER....................................................6 OPERATION..................................................................................................7 MAINTENANCE ............................................................................................8 BATTERY REPLACEMENT ..........................................................................9 SPECIFICATIONS ......................................................................................10 2 ...

Page 3

... AMPROBE Tel: 305-423-7500 Fax: 305-423-7554 Tech. Support: 1-800-327-5060 Outside the U.S.A. the local Amprobe representative will assist you. Above limited warranty covers repair and replacement of instrument only and no other obligation is stated or implied. 3 instrument. It has ® ...

Page 4

... Flexible Transducer in the vicinity of these hazardous potentials The AMPROBE Flexible AC Current Transducer Model assembly similar in purpose to a CTor current transformer. It may be used to measure AC currents from as low as several amps to a maximum of 3.0kA rms. The device output is an analog voltage that is proportional to the current in the conductor ...

Page 5

... An external DC power supply is available for this purpose but is sold as an option . The power required is +3.0VDC/10mA. FLEXIBLE AC CURRENT TRANSDUCER Fig ACF-3000DM ELECTRONICS PACKAGE Fig ACF-5A: OUTPUT SIGNAL SUPPLIED ADAPTER FOR THE DM-II™ 5 Fig ACF-5CE: OUTPUT SIGNAL SUPPLIED ADAPTER FOR DM-II PRO & DM-II CE ...

Page 6

... AC Current This transducer is a versatile current probe that may be wrapped around most conductors. Its application versatility and high- voltage isolation rating clearly distinguish the ACF-3000DM from other current measuring methods. The measuring transducer is constructed from nonfer- rous materials, minimizing any circuit loading. ...

Page 7

... There is minimal shock hazard using the ACF-3000DM-A, as the transducer does not generate high voltages at low frequencies. Each transducer has been Hi-Pot tested to several thousand volts with no voltage breakdown particular characteristic allows high-current measurement (with a wide frequency bandwidth) of conductors at less than 600VAC potential to earth ...

Page 8

... 300ARange: 1.0mVAC/Amp 3000A Range: 0.1mVAC/Amp Return the ACF-3000 range switch to the OFF position when measurement is completed to preserve battery life Preventive maintenance primarily consists of cleaning the transducers and cables to prevent surface contamination. Use a mild detergent and water to clean the transducers and cables. Remove the detergent with clear water, then wipe dry with a clean cloth ...

Page 9

... Replace batteries (note the polarization marked on the bottom of the bat- tery compartment). 4) Replace the cover of the battery compartment Turn a lock from open to close position ! ! SAFETY WARNING ! ! Before removing the battery cover, make sure that the Flexible AC Current Transducer is removed from around any active conductor. Fig BACK OF ACF-3000DM-AW/ BATTERY COVER REMOVED 9 ...

Page 10

Measuring Ranges: 300A/3000A Output Sensitivity: 1mV/0.1mV/A (AC coupled) Accuracy: (at 25°C) ±1% of range Frequency Range: 10Hz to 5kHz Phase Error: ±1º ( Hz), ±10º ...

Page 11

11 ...

Page 12

... Miami, Florida Phone: 305-423-7500 Fax: 305-423-7554 www.amprobe.com AMPROBE ® 12 Printed in U.K. ...