256-TWMU-QQHG-C6-SS Tyco Electronics, 256-TWMU-QQHG-C6-SS Datasheet - Page 2

TRANSDUCER, WATT, 400HZ, CURRENT

256-TWMU-QQHG-C6-SS

Manufacturer Part Number
256-TWMU-QQHG-C6-SS
Description
TRANSDUCER, WATT, 400HZ, CURRENT
Manufacturer
Tyco Electronics
Datasheet

Specifications of 256-TWMU-QQHG-C6-SS

Transducer Function
Watt
Transducer Input Current Ac
5A
Transducer Output Type
Current
Frequency
400Hz
Terminal Type
3-wire
Supply Voltage
120VAC
Input Current
5mA
Power Load Type
Unbalanced
Lead Free Status / RoHS Status
na
Paladin Transducers 250 Series Class 0.5
Specification
Performance
Temperature Range:
Temperature Coefficient:
Humidity Range:
Zero Adjustment:
Span Adjustment:
Accuracy Class:
Accuracy Range:
Stability:
Test Voltage:
Response Time:
D.C. outputs (Typical):
Current Output Protection: Fully protected against open and short circuited output
Voltage Output Protection: Fully protected against open circuit output
Maximum output:
Output Ripple:
Overoad Capacity:
Input Impedance:
(d.c. I/P)
Input Burden:
Auxiliary Burden:
Safety:
Minimum Test Voltage:
Flammability:
Isolation:
Interference:
Immunity:
Enclosure:
Fixing:
Approvals:
10
Designed to comply with BS6253 part 1, EN60688,
IEC688, AS1384 and ANSI. C37.
Storage -20°C to +70°C
Operating 0°C to +60°C
Calibrated at 23°C
0.03%/ per °C
Up to 95% RH
±2% minimum (except TAA & TVA)
±10% minimum
0.5 unless otherwise specified
0 to 125% (except self powered)
+0.25% per annum (reducing with time)
2kV ms to ANSI, C37
<400ms from 0 to 99% of rated output, 250 ms to 90%
0/1mA into 0-10kΩ
0/5mA into 0-2kΩ
0/10mA into 0-1kΩ
0/20mA into 0-500Ω (600Ω available on selected models)
4/20mA into 0-500Ω (600Ω available on selected models)
0/5V 1k ohm minimum load
0/10V 1K ohm minimum load - bipolar for some models
20V d.c. when open circuit
<0.5% of full rated output
2 x rated current continuous
1.25 x rated voltage continuous
20 x rated current for 1 second
1.5 x rated voltage for 10 seconds
d.c. 1000 ohms/volt as standard
10k ohms/volt available on request
a.c. <2VA
<2VA a.c., <3.5W d.c.
auxiliary voltage variation: ±20% a.c., ±15% d.c.,
maximum 14% ripple
To IEC1010 with terminal cover, basic insulation category
2kV rms for 1 minute
Flame retardant
Input/Output/Supply/Case (except TRR, TRP, TRT and
TRV with no input/output isolation)
Electrical stress surge withstand to IEC 688 part of IEC 801
and ANSI C37 90a
Impulse test 5kV transient to IEC688 and IEC801
IP50 to BS5490, IEC529 when the terminal cover is
fitted. The case is UL94V0 and the terminal cover is
UL94V2
EN50022
EMC and LVD
UL recognised File No: E140758
CSA recognised File No: LR52592
BV File No: 3896H-07425-AO PRSO BV

Related parts for 256-TWMU-QQHG-C6-SS