C200HW-PRM21 Omron, C200HW-PRM21 Datasheet - Page 22

no-image

C200HW-PRM21

Manufacturer Part Number
C200HW-PRM21
Description
MASTER MODULE
Manufacturer
Omron
Datasheets

Specifications of C200HW-PRM21

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
J Features
Item
Applicable Standard
Network Media/Topology
Connector
Cable Length/Transmission Rate
I/O Available per PLC
Error Reporting
Supported FINS Messages
Supported Services
CPU bus module where up to 16 masters can be
mounted per PLC.
Supports cyclic communications with up to 125 slave
stations per network.
Total size of I/O data for all ProfiBus masters mounted
per PLC must not exceed 7,168 words.
Utilizes FDT/DTM Technology:
ProfiBus allows for multiple masters per network and
utilizes a token passing procedure which allows the
token possessing master to poll its assigned slaves.
ProfiBus Configurator enables easy monitoring of the
status and settings for network devices, and provides
error information for the master.
--
--
g /
FDT (Field Device Tool): An FDT container ap-
plication (ie. CX-ProfiBus) allows for configura-
tion, manipulation and monitoring of network
nodes.
DTM (Device Type Managers): A Microsoft
COM-component provided by the device manag-
er that allows for interactive configuration and
diagnostics, similar to a printer driver.
CJ1W-PRM21
DeviceNet Module
Description
EN 50170 Part 2 (ProfiBus-DP)
RS-485 Bus, 125 slave node stations max.
Female D-Sub 9-pin
Baud Rate (kbit/s) Distance/segment (m)
9.6
19.2
45.45
93.75
187.5
7,168 words max. (for all ProfiBus masters connected to one PLC)
Max. of 80 error events can be logged
MEMORY AREA READ
ERROR LOG READ
ERROR LOG CLEAR
RUN
STOP
Set_PRM
Chk_Cfg
Slave_Diag
Data_Exchange
Global_Control (FREEZE, UNFREEZE, SYNC, UNSYNC, CLEAR)
Industrial Networking and Communications
1200
1200
1200
1200
1000
ProfiBus-DP (PROcess FIeld BUS -- Decentralized Periph-
ery) is a vendor-independent, open fieldbus standard for a
wide range of applications in manufacturing, process and
building automation. Vendor independence and transparen-
cy of operation are guaranteed by the ProfiBus standard
EN50170. With ProfiBus, devices of different manufacturers
can communicate without special interface adjustments.
J Diagnostic Messages
Note: ProfiBus master modules support the storage of up to 80
J Troubleshooting
Device Related Diagnostics: Messages to determine
the operational status of the whole device (ie. over tem-
perature, low voltage)
Module Related Diagnostics: Messages to identify an
error in a specific range of I/O for a slave station (ie. an
8-bit output module)
Channel Related Diagnostics: Messages indicating an
error at a given input or output (ie. short circuit on out-
put 5)
Extensive self-diagnostic function at startup
Dedicated status flags, indicating if I/O data is being
exchanged within the assigned slave stations
Dedicated status flags, indicating if new slave diagnos-
tic data is available
Extensive status and error flags, indicating the status of
the module and the ProfiBus network
Error log for recording error history data
error events.
Programmable Controller
ProfiBus-DP Master Module
Baud Rate (kbit/s) Distance/segment (m)
500
1500
3000
6000
12000
400
200
100
100
100
CJ1