E53-CK01 Omron, E53-CK01 Datasheet - Page 3

no-image

E53-CK01

Manufacturer Part Number
E53-CK01
Description
COMPUTER COMMUNICATION OUTPUT BOARD
Manufacturer
Omron
Type
Ramp / Soak Process Controllerr
Datasheets

Specifications of E53-CK01

Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Mounting Type
Panel
Supply Voltage Max
240VAC
Supply Voltage Min
100VAC
Control Method
ON/OFF and PID Control
Voltage Rating
240 V
Mounting
Horizontal Mount
Display Type
7-Segment
Features
Modular structure, one-stock type
Input Type
Analog
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E53CK01
J Characteristics
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°C max. is ±2°C ±1 digit maximum. The
Indication accuracy
(S
(See Note 1)
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Set time
Program capacity
Programming method
Time accuracy
Sampling period
(S
(See Note 2)
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Enclosure ratings
Memory protection
Weight
EMC
Approved standards
A--182
p
2. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
N t 1)
N t 2)
g p
indication accuracy of the U and L thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C max. is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is great-
er) ±1 digit maximum. The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is
greater) ±1 digit maximum.
p
Ramp/Soak Process Controller
g
y
Thermocouple
Platinum
resistance
thermometer
Analog input
Temperature input
Analog input
Malfunction
Destruction
Malfunction
Destruction
Operating
Storage
Operating
Front panel
Rear case
Terminals
±0.3% of indication value or ±1°C, whichever greater, ±1 digit max.
±0.2% of indication value or ±0.8°C, whichever greater, ±1 digit max.
±0.2% of indication value, ±1 digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
0 to 99 hrs 59 min or 0 to 99 min 59 s
1 pattern, 16 steps (possible to use up to 4 patterns with the communications func-
tion.)
Time or ramp setting method
±0.2% (±500 ms) of the set value
250 ms
100 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
10 to 55 Hz, 10 m/s
10 to 55 Hz, 20 m/s
200 m/s
applied to the relay)
300 m/s
35% to 85%
NEMA 4 for indoor use (equivalent to IP66)
IEC standard IP20
IEC standard IP00
Non-volatile memory (number of writings: 100,000 operations)
Approx. 170 g;
Adapter: approx. 10 g
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered
terminal cover is mounted.
--1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on input type)
--10°C to 55°C (with no icing)/3-year warranty period: --10°C to 50°C
--25°C to 65°C (with no icing)
E5CK- -T
2
2
min. (approx. 20G), 3 times each in 6 directions (100 m/s
min. (30G), 3 times each in 6 directions
2
2
(approx. 1G) for 10 min each in X, Y, and Z directions
(approx. 2G) for 2 hrs each in X, Y, and Z directions
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2:
ENV50140:
EN61000-4-4:
4kV contact discharge (level 2)
8kV air discharge (level 3)
10V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900
MHz)
10V (0.15 to 80 MHz ) (level 3)
2kV power-line (level 3)
2kV I/O signal-line (level 4)
2