XTAE007B10TD3E008 EATON CUTLER HAMMER, XTAE007B10TD3E008 Datasheet - Page 165

IEC Non-Reversing Starter

XTAE007B10TD3E008

Manufacturer Part Number
XTAE007B10TD3E008
Description
IEC Non-Reversing Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTAE007B10TD3E008

No. Of Phases
Single Or Three
Power Rating
3.5kW
Current Rating
7A
Operating Temperature Range
-25°C To +50°C
Mounting Type
DIN Rail
Overload Adjustment Current Max
8A
Overload Adjustment Current Min
1.6A
Supply Voltage Max
24VDC
Frame Size
Standard
Frame B
Frame D
XTPR Manual Self-Protected Motor Starters—North American Ratings, UL 508 Type E—Frame B
Motor Protective Device with Thermal and Magnetic Trip
Rated
Uninterrupted
Current—
I
0.16
0.25
0.4
0.63
1
1.6
2.5
4
6.3
10
12
16
20
25
32
XTPR Manual Self-Protected Motor Starters—North American Ratings, UL 508 Type E—Frame D
Motor Protective Device with Thermal and Magnetic Trip
Rated
Uninterrupted
Current—
I
16
25
32
40
50
58
65
Notes
A UL 508 Type E self-protected manual combination starter (XTPR) consists of a manual motor protector (XTPR) and a UL Listed line side adapter (e.g., XTPAXLSA).
The Type E self-protected manual combination starter alone is a legitimate short-circuit protective device and disconnect means for the downstream motor,
while the contactor has been added to provide remote operation of the motor circuit. Conductor size for XTPAXLSA is 14–6 AWG, XTPAXLSAD is 8 AWG–1/0.
u
u
(Amps)
(Amps)
UL 508 Type E starters are assembled from a standard XTPR and a special incoming terminal line side adapter (XTPAXLSA or XTPAXLSAD).
Select manual motor protectors by full load amperes. Maximum motor ratings (kW, hp) are for reference only.
In this range, calculate motor rating according to rated current. Specified values to NEC 430.6(A)(1).
FLA
Adjustment
Range/
Overload
Release—
I
0.1–0.16
0.16–0.25
0.25–0.4
0.4–0.63
0.63–1
1–1.6
1.6–2.5
2.5–4
4–6.3
6.3–11
8–12
10–16
16–20
20–25
25–32
FLA
Adjustment
Range/
Overload
Release—
I
10–16
16–25
25–32
32–40
40–50
50–58
55–65
r
r
(Amps)
(Amps)
Volume 5—Motor Control and Protection CA08100006E—May 2011 www.eaton.com
Short
Circuit
Release—
I
2.2
3.4
5.6
8.8
14
22
35
56
88
140
168
224
280
350
448
Short
Circuit
Release—
I
224
350
448
560
700
812
882
rm
rm
(Amps)
(Amps)
Maximum Motor Ratings
Maximum hp Rating—P (hp)
Three-Phase
200V
1/2
3/4
1
3
3
3
5
5
7-1/2
Maximum Motor Ratings
Maximum hp Rating—P (hp)
Three-Phase
200V
3
7-1/2
10
10
240V
1/2
1
1-1/2
3
3
5
5
7-1/2
10
240V
5
7-1/2
10
15
IEC Contactors and Starters
480V/
277V
1/2
1/2
1/2
1/2
1/2
3/4
1
2
3
7-1/2
7-1/2
10
15
25
480V/
277V
10
20
25
30
30
40
40
600V/
247V
1/2
1/2
1/2
1/2
1/2
3/4
1-1/2
3
5
10
600V/
247V
10
25
30
30
Rated Short-Circuit
Breaking Capacity (kA)
240V
65
65
65
65
65
65
65
65
65
65
65
42
18
18
18
Rated Short-Circuit
Breaking Capacity (kA)
240V
65
65
65
65
65
65
65
XT IEC Power Control
480/
277V
65
65
65
65
65
65
65
65
65
65
65
42
18
18
18
480/
277V
65
65
65
65
65
65
65
600/
347V
50
50
50
50
50
50
50
50
50
50
600/
347V
25
25
25
25
Line Side
Adapter
Catalog Number
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
XTPAXLSA
Line Side
Adapter
Catalog Number
XTPAXLSAD
XTPAXLSAD
XTPAXLSAD
XTPAXLSAD
XTPAXLSAD
XTPAXLSAD
XTPAXLSAD
Manual Motor
Protector—
Screw Terminal
Catalog Number
XTPRP16BC1
XTPRP25BC1
XTPRP40BC1
XTPRP63BC1
XTPR001BC1
XTPR1P6BC1
XTPR2P5BC1
XTPR004BC1
XTPR6P3BC1
XTPR010BC1
XTPR012BC1
XTPR016BC1
XTPR020BC1
XTPR025BC1
XTPR032BC1
Manual Motor
Protector—
Screw Terminal
Catalog Number
XTPR016DC1
XTPR025DC1
XTPR032DC1
XTPR040DC1
XTPR050DC1
XTPR058DC1
XTPR063DC1