PAXCDS20 Red Lion Controls, PAXCDS20 Datasheet

Quad Setpoint Relay Output Interface Card

PAXCDS20

Manufacturer Part Number
PAXCDS20
Description
Quad Setpoint Relay Output Interface Card
Manufacturer
Red Lion Controls
Datasheets

Specifications of PAXCDS20

Accessory Type
Quad Setpoint Relay Output Interface Card
Accuracy
± 0.01% + 10 ms
Brand/series
PAX Series
Card Type
Quad Setpoint Relay Output Card
Contact Rating
One Relay Energized: 3 Amps @ 250 VAC or 30 VDC, 1⁄10 HP @ 120 VAC
Number Of Outputs
4
Output Type
Form-A Relays
Standards
cULus Listed, CSA Certified and CE Marked
Voltage, Working
125 V
Pax Label Kit
189 Different Engineering Units, Labels Inserted Inside the Unit
For Use With
Red Lion PAX Digital Input Panel Meters
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
DESCRIPTION
operation of PAX Setpoint cards. The setpoint cards are available as dual relay,
quad relay, quad sourcing transistor, or quad sinking transistor outputs. Only
one setpoint card can be installed at a time.
MODEL PAXCDS -SETPOINT OUTPUT PLUG-IN OPTION CARDS
INSTALLING AN OPTION CARD
1. Remove the main assembly from the rear of the case. Squeeze the finger
2. Locate the option card connector for the type of option card to be
3. Install the option card by aligning the option card connector with the slot
4. Slide the assembly back into the case. Be sure the rear cover latches fully
5. Apply the option card label to the bottom side of the meter. Do not cover
This bulletin serves as a guide for the installation, configuration and
holds on the rear cover, or use a small screwdriver to depress the side
latches to release it from the case. It is not necessary to separate the rear
cover from the main circuit card.
installed. Hold the unit by the rear connector, not the display board, when
installing an option card.
in the rear cover. The cards are keyed by position with different main
board connector locations. Be sure the connector is fully engaged and the
tab on the option card rests in the alignment slot on the display board.
into the case.
the vents on the top surface of the meter. The surface of the case must
be clean for the label to adhere properly. Apply the label to the area
designated by the large case label.
Caution: The option and main circuit cards contain static
sensitive components. Before handling the cards, discharge
static charges from your body by touching a grounded bare metal
object. Ideally, handle the cards at a static controlled clean
workstation. Also, only handle the cards by the edges. Dirt, oil or
other contaminants that may contact the cards can adversely
affect circuit operation.
Warning: Exposed line voltage exists on the circuit boards.
Remove all power to the meter AND load circuits before
accessing the unit.
1
the option cards are dedicated to a particular card function. The option card
functions are: serial communications, analog output and setpoint output. Only
one card from each function category can be installed.
The PAX meter can be fitted with up to three option cards. The slot bays of
PAX REAR TERMINAL CONNECTIONS
TOP VIEW
Bulletin No. PAXCDS-E
Drawing No. LP0400
Released 11/07

Related parts for PAXCDS20

PAXCDS20 Summary of contents

Page 1

Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL PAXCDS -SETPOINT OUTPUT PLUG-IN OPTION CARDS DESCRIPTION This bulletin serves as a guide for the installation, configuration and operation of PAX Setpoint cards. The setpoint cards are available as dual ...

Page 2

... Total Current With Both Relays Energized not to exceed 5 amps Life expectancy: 100 K cycles min. at full load rating. External RC snubber extends relay life for operation with inductive loads Quad Relay Card: PAXCDS20 Type: Four FORM-A relays Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min. ...

Page 3

SETPOINT ACTION OFF Ab-HI Ab-LO dE-HI dE-LO bANd Enter the action for the selected setpoint (alarm output). See Setpoint Alarm Figures for a visual detail of each action. = Setpoint always off, (returns to SPSEL NO) = Absolute high, with ...

Page 4

... The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC ...