MPAXD000 Red Lion Controls, MPAXD000 Datasheet - Page 26

no-image

MPAXD000

Manufacturer Part Number
MPAXD000
Description
Voltage-Current Input Module
Manufacturer
Red Lion Controls
Datasheets

Specifications of MPAXD000

Accessory Type
Analog Input Module
Signal Input Type
Selectable Voltage
No. Of Analog Outputs
5
Character Size
0.56"
Accuracy
0.03% of reading + 0.03 μA to 0.5% of reading + 0.3 μA @ 18 to 28 °C, 0.03% of reading +30 μV to 0.05% of reading +30 mV @ 18 to 28 °C, 0.05% of reading +30 Megohm to 0.05% of reading +1 Ohms @ 18 to 28 °C
Brand/series
MPAX Series
Display Type
LED
Impedance, Input
100 Ohms to 10 Kiloohms
Measuring Range
± 200 μADC to ± 2 ADC, ± 200 mVDC to ± 300 VDC, 100 Ohms to 10 Kiloohms
Resolution
10 nA to 0.1 mA, 10 μV to 10 mV, 0.01 Ohms to 1 Ohms
Standards
cULus Listed, CE Certified
Voltage, Working
85 to 250 VAC
Sealing
NEMA 4/IP65
No. Of Analog Inputs
5
Rohs Compliant
Yes
For Use With
EPAX 5 Digit Displays
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
TROUBLESHOOTING
PARAMETER VALUE CHART
PAX MODEL NUMBER
* Decimal point location is model and programming dependent.
DISPLAY
1-INP
rAN6E
tyPE
SCALE
COUPL
dECPt
round
OFFSt
FILtr
bANd
ICE
PtS
StYLE
INP 1
dSP 1
INP 2
dSP 2
INP 3
dSP 3
INP 4
dSP 4
INP 5
dSP 5
PROBLEM
NO DISPLAY
PROGRAM LOCKED-OUT
MAX, MIN, TOT LOCKED-OUT
INCORRECT INPUT DISPLAY VALUE
“OLOL” in DISPLAY (SIGNAL HIGH)
“ULUL” in DISPLAY (SIGNAL LOW)
JITTERY DISPLAY
MODULES or PARAMETERS NOT ACCESSIBLE
ERROR CODE (Err 1-4)
DISPLAY ZERO’S AT LEVELS BELOW 1% OF RANGE
Signal Input Parameters
PARAMETER
MODEL DEPENDENT
PAXT: INPUT TYPE
PAXT: TEMPERATURE SCALE
PAXH: INPUT COUPLE
* DISPLAY RESOLUTION
DISPLAY ROUNDING INCREMENT
PAXT: DISPLAY OFFSET
FILTER SETTING
FILTER ENABLE BAND - PAXH
PAXT: ICE POINT SLOPE
SCALING POINTS
SCALING STYLE - NOT PAXT
* INPUT VALUE 1
* DISPLAY VALUE 1
* INPUT VALUE 2
* DISPLAY VALUE 2
* INPUT VALUE 3
* DISPLAY VALUE 3
* INPUT VALUE 4
* DISPLAY VALUE 4
* INPUT VALUE 5
* DISPLAY VALUE 5
For further assistance, contact technical support at the appropriate company numbers listed.
-
PAXH
0. 0 20
0. 5
________ Meter# _____________ Security Code __________
FACTORY
SETTING
tc-.
0. 0 00
1. 0 00
1000
0. 0 00
0. 0 00
0. 0 00
0. 0 0
KEY
°F
AC
1. 0
10
0
1
0
2
0
0
0
0
REMEDIES
CHECK: Power level, power connections
CHECK: Active (lock-out) user input
ENTER: Security code requested
CHECK: Module 3 programming
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
PERFORM: Module 9 Calibration (If the above does not correct the problem.)
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
CHECK: Corresponding plug-in card installation
PRESS: Reset KEY (If cannot clear contact factory.)
PROGRAM: Module 4 as Hi-t: 0.0 LO-t: 3271.1 (to disable zero chop feature)
USER SETTING
Programmer ________________ Date ________
Module 4 Display Offset is zero, press DSP for Input Display
25
DISPLAY
INP 6
dSP 6
INP 7
dSP 7
INP 8
dSP 8
INP 9
dSP 9
INP 10
dSP 10
INP 11
dSP 11
INP 12
dSP 12
INP 13
dSP 13
INP 14
dSP 14
INP 15
dSP 15
INP 16
dSP 16
PARAMETER
* INPUT VALUE 6
* DISPLAY VALUE 6
* INPUT VALUE 7
* DISPLAY VALUE 7
* INPUT VALUE 8
* DISPLAY VALUE 8
* INPUT VALUE 9
* DISPLAY VALUE 9
* INPUT VALUE 10
* DISPLAY VALUE 10
* INPUT VALUE 11
* DISPLAY VALUE 11
* INPUT VALUE 12
* DISPLAY VALUE 12
* INPUT VALUE 13
* DISPLAY VALUE 13
* INPUT VALUE 14
* DISPLAY VALUE 14
* INPUT VALUE 15
* DISPLAY VALUE 15
* INPUT VALUE 16
* DISPLAY VALUE 16
FACTORY
SETTING
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0. 0 00
0
0
0
0
0
0
0
0
0
0
0
USER SETTING

Related parts for MPAXD000