LPAX0500 Red Lion Controls, LPAX0500 Datasheet - Page 4

Multifunction Meter

LPAX0500

Manufacturer Part Number
LPAX0500
Description
Multifunction Meter
Manufacturer
Red Lion Controls
Type
Multi-Functionr
Datasheet

Specifications of LPAX0500

No. Of Digits / Alpha
5
Panel Cutout Height
3.63"
Panel Cutout Width
9.29"
Signal Input Type
Current, Process, Strain Gage, Thermocouple, Voltage
Connection Type
Cage-Clamp
Cut Out, Panel
9.29×3.63 "
Digit Height
4
Dimensions
10"L×4.77"W×4.75"H
Display Digit Height
1.5 "
Display Type
LED
Function
Ammeter/Process/Resistance/Strain Gage/Temperature/Voltage
Material, Casing
Steel
Number Of Digits
6
Primary Type
Electronic
Range, Measurement
-19999 to 99999
Termination
Cage Clamp
Voltage, Input
85 to 250 VAC
Voltage, Supply
85 to 250 VAC/11 to 36 VDC or 24 VAC
Sealing
NEMA 4/IP65
Character Size
1.5"
Color
Red
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
Red Lion MPAXD000, MPAXH000, MPAXP000 And MPAXT000 MPAX Modules
LPAX DISPLAY INSTALLATION
enclosure. The display is provided with a gasket to provide a
water-tight seal. The recommended minimum panel thickness
for NEMA 4/IP65 sealing is 0.060" (1.57 mm).
dimensions shown. The supplied template may be used to
mark the cut-out and hole locations on the panel. After
the panel cut-out has been deburred, slide the panel
gasket over the rear of the display and onto the
mounting studs. Insert the display into the panel
cut-out as illustrated in Figure 3. Install six # 10-32
keps nuts (supplied) and tighten evenly for uniform
gasket compression. Do not over-tighten the nuts.
LPAX can be surface-wall mounted, suspended, or
bottom mounted. Separate installation instructions
are provided with the mounting accessories.
Environment And Cleaning
does not exceed the maximum operating temperature
and provides good air circulation. Placing the system
near devices that generate excessive heat should be
avoided.
and neutral soap product. Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate
the aging process of the bezel.
capabilities of our PAX Series Intelligent Panel Meters. Therefore, you will find
the appropriate PAX information packed with the MPAX Module. Simply
follow the instructions to wire and program the display for your application.
2.0 INSTALLING THE DISPLAY
3.0 WIRING AND PROGRAMMING THE DISPLAY
The LPAX display is intended to be mounted into a panel or
For panel mounting, prepare the panel cut-out to the
By using additional mounting accessories, the
The display should be installed in a location that
The bezel should be cleaned only with a soft cloth
Once assembled, the LPAX and MPAX have all the same functions and
ORDERING INFORMATION
* See the LPAX Accessory Bulletin or our web site for available units labels.
** Crimson software is available for download from http://www.redlion.net/
Accessories
Optional
Display
Analog
Module
Plug-In
Cards
TYPE
Input
MODEL NO.
SFCRD**
PAXCDS
PAXCDC
PAXCDL
MPAX
LPAX
ENC9
SHR
LX
MB
*
5-Digit, Large Display for Analog MPAX Modules
Universal DC Input Module, AC Powered
Universal DC Input Module, DC/24 VAC Powered
Process Input Module, AC Powered
Process Input Module, DC/24 VAC Powered
Thermocouple and RTD Module, AC Powered
Thermocouple and RTD Module, DC/24 VAC Powered
AC True RMS Voltage and Current Module, AC Powered
Strain Gage Input Module, AC Powered
Strain Gage Input Module, DC/24 VAC Powered
Dual Setpoint Relay Output Card
Quad Setpoint Relay Output Card
Quad Setpoint Sinking Open Collector Output Card
Quad Setpoint Sourcing Open Collector Output Card
RS485 Serial Communications Output Card with Terminal Block
Extended RS485 Serial Communications Output Card with Dual RJ11 Connector
RS232 Serial Communications Output Card with Terminal Block
Extended RS232 Serial Communications Output Card with 9 Pin D Connector
DeviceNet Communications Card
Modbus Communications Card
Extended Modbus Communications Card with Dual RJ11 Connector
Profibus-DP Communications Card
Analog Output Card
Custom Units Label
Crimson 2 PC Configuration Software for Windows 98, ME, 2000 and XP
NEMA 4 Enclosure for LPAX
Shroud for LPAX
Mounting Bracket for LPAX
DESCRIPTION
Figure 3, Installing The LPAX Into A Panel
TROUBLESHOOTING
For technical assistance, contact technical support.
Listed Separately
PART NUMBERS
MPAXD000
MPAXD010
MPAXH000
MPAXP000
MPAXP010
MPAXT000
MPAXT010
MPAXS000
MPAXS010
PAXCDC1C
PAXCDC2C
PAXCDC4C
LPAX0500
PAXCDC10
PAXCDC20
PAXCDC30
PAXCDC40
PAXCDC50
PAXCDS10
PAXCDS20
PAXCDS30
PAXCDS40
PAXCDL10
SFCRD200
SHRLPAX0
MBLPAX00
ENC90000

Related parts for LPAX0500