KWH-400 Tyco Electronics, KWH-400 Datasheet - Page 3

KWH METER, 3 PHASE

KWH-400

Manufacturer Part Number
KWH-400
Description
KWH METER, 3 PHASE
Manufacturer
Tyco Electronics
Datasheet

Specifications of KWH-400

Meter Function
Kilowatt Hour Energy
Meter Size/dimensions
96mm X 96mm X 82mm
External Depth
82mm
External Length / Height
96mm
External Width
96mm
Ip/nema Rating
IP 54
Input Voltage Max
400V
Operating
RoHS Compliant
Programming and Scaling
The KWH-400 is direct connected up to
500V with 5 Amp CT inputs. The CT ratio
is field programmable without any
special tools via DIP switches mounted
on the underside of the unit behind a
tamper proof label.
Once the CT ratio has been
programmed, the scale factor should be
adjusted on the front display. A self-
adhesive decimal point can be affixed in
the appropriate position on the
mechanical counter.
KWH-400 – DIN Panel Mounted Kilowatt Hour Energy Meter
CT Ratio
5/5A
10/5A
20/5A
30/5A
40/5A
50/5A
60/5A
75/5A
80/5A
100/5A
125/5A
150/5A
200/5A
250/5A
300/5A
400/5A
500/5A
600/5A
750/5A
800/5A
1000/5A
1200/5A
1250/5A
1500/5A
1600/5A
2000/5A
2500/5A
3000/5A
3200/5A
4000/5A
5000/5A
4
1
1
1
1
1
1
1
1
0
1
0
1
1
0
1
1
1
1
1
0
1
0
0
1
0
1
0
1
1
1
1
DIP Switch
Setting
3
1
1
1
1
0
1
0
0
1
1
1
0
1
1
1
0
1
0
0
1
1
1
1
0
0
1
1
1
1
0
1
2
1
1
0
0
1
1
1
0
1
1
0
0
0
1
0
1
1
1
0
1
1
0
0
0
1
0
1
0
0
1
1
1
1
0
1
0
1
1
0
1
0
0
0
0
1
1
0
1
1
0
1
0
0
1
0
0
1
1
1
0
1
1
1
Multiplier
0.01
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
1
1
1
1
1
1
1
1
1
1
1
10
10
10
10
10
10
10
10
10
10
10
Specification
Product Codes
Connections
L1
L2
L3
It is recommended that all voltage lines are fitted with 1 Amp HRC fuses. For safety
reasons, CT secondary connections should be grounded according to local codes of
practice.
Active Energy Accuracy:
Auxiliary Supply:
Input Frequency:
Nominal Input Voltage:
Input Voltage Tolerance:
Nominal Input Voltage Burden:
Nominal Input Current:
Start Up Current:
Max Continuous Input Current:
Nominal Input Current Burden:
Power Factor:
Current Measurement:
System CT Primary Ratios:
Pulsed Output:
Pulse Capacity:
Pulse Duration:
Counter:
Reading Resolution:
LED Indicator Display:
Pulse Indicator:
Enclosure Style:
Enclosure Material:
Terminals:
Fixing:
Compliant With:
Operating Temperature:
Storage Temperature:
Relative Humidity:
Dimensions:
Panel Cut Out:
IP Protection:
Weight:
Order Code
KWH-400-110
KWH-400-400
3 Phase 3 Wire Unbalanced Load
S1
P1
S1 S2
S1
P1
S1 S2 L1 L2 L3
PULSE
OUTPUT
+
+ _
_
L
O
A
D
Class 1.0 +/- 1.0% of range maximum
Self powered
45 - 55HZ
110V – 400V L-L (63.5 – 230V L-N)
85 - 500V L-L (49 – 288V L-N)
<8VA
5A
0.2% of rated current
6A
<2 VA
0.5 lag – unity – 0.8 lead
3 x current transformers (not included)
5, 10, 20, 30, 40, 50, 60, 75, 100, 150, 200, 250,
300, 400, 500, 600, 800, 1000, 1200, 1250, 1500,
1600, 2000, 3200, 5000A
Volt free optical Isolator with open collector
transistor output
50V DC, <40mA
>200 milli seconds
6 digit auto-resetting electro-mechanical
1 per kW.h
3 x Green: Voltage phase monitoring
3 x Red: Reverse connected CT warning
Red LED flashing at rate proportional to the
measured power
Panel mount to DIN 42700
Glass filled polycarbonate
M4 captive screw clamp
2 side clamps
IEC 1036. EMC and LVD
0 to +55°C
-10 to +70°C
0 .. 95% non condensing
96mm high x 96mm wide x 82mm deep
92mm x 92mm
IP54
500g approx
Description
3 phase 3 and 4 wire, CT Connected 5A 110V L/L
3 phase 3 and 4 wire, CT Connected 5A 400V L/L
L1
L2
L3
N
S1
3 Phase 4 Wire Unbalanced Load
P1
S1 S2
P1
S1 S2
S1
S1
P1
S1 S2 L1 L2 L3
N
+
PULSE
OUTPUT
+ _
_
L