5016R-300VAC HOYT ELECTRICAL INSTRUMENT, 5016R-300VAC Datasheet - Page 7

Voltage Meter

5016R-300VAC

Manufacturer Part Number
5016R-300VAC
Description
Voltage Meter
Manufacturer
HOYT ELECTRICAL INSTRUMENT
Datasheet

Specifications of 5016R-300VAC

Meter Function
AC Voltmeter
Meter Range
0-300 VAC
Meter Size/dimensions
1.5 In
Meter Shape
Square
Voltage Meter Range
0-300 VAC
Display Accuracy ±
3%
Accuracy
+/-2 %
Barrel Size
1.50"
Meter Movement
Moving Coil
Lead Free Status / RoHS Status
na
DONUT TYPE HIGH CURRENT TRANSFORMERS
These transformers may be used with any 5 AC
ampere Hoyt meter. They have a 5 ampere
secondary and are made in primary ranges up
to 600 amperes for mounting over the bus bar
or high current wire to be measured.
Connecting leads are 24” long. Capacity is 2VA
insulated to 4500 volts. CT’s up to 600 amperes
size is 4” in diameter with a 1-1/4” hole; 700 to
1000 amperes have an overall
diameter of 4” with 1-3/4” hole.
Higher current available.
There are models of various shapes, sizes and
VA ratings to fit every application. In sizes from
.4” to 11.75” id. Standard ANSI class.
Models include:
Specialty, Solid Core, Specific Mounting, Rectan-
gular, Wound Primary, Flexible (Split Core),
Three Phase, Multi Ratio & Potential.
Hoyt Electrical Instrument Works, Inc. Penacook, NH
(800) 258-3652 Fax (603) 753-9592 WWW.HOYTMETER.COM
Instrument Transformers
Features & Benefits
Applications
Voltage Transformers
Wound Primary
Fully encapsulated, rubber molded
Indoor or outdoor applications
UL & CUL Recognize Standards
Standard Output: 5A
Optional 0.100A, 0.200A or 1.0A
secondary for electronic devices
Custom designs available
600 Volt Instrument Transformers
Current Transformers
Flexible Split Core
7