Specifications of E5AN-R3MT-500-N AC100-240

No. Of Digits / Alpha
4
Meter Function
Temperature
Meter Range
-200°C To +2300°C
Digit Height
15.8mm
Power Consumption
10VA
Operating Temperature Range
-10°C To +55°C
No. Of Outputs
3
Supply Voltage Range
100VAC To 240VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications Table
J Communications Specifications
Note: 1. RS-232C communications are only supported for the E5AN and E5EN models.
J Current Transformer Ratings
Note: 1. Use within the max heater current rating of controller table shown below.
J Heater Burnout Alarm
Note: 1. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
A--78
Dielectric strength
Vibration resistance
Shock resistance
Weight
Protective structure
Memory protection
EMC
Approved standards
Transmission path connection
Communications method (See Note 1)
Synchronization method
Baud rate
Transmission code
Data bit length (See Note 2)
Stop bit length (See Note 2)
Error detection
Flow control
Interface (See Note 1)
Retry function
Communications buffer
Model
Max. continuous heater current
Dielectric strength
Vibration resistance
Weight
Accessories
Max. heater current
Heater current value display accuracy ±5% FS ±1 digit max.
Heater burnout alarm setting range
Min. detection ON time
2. The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
2. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less
than 190 ms.
Digital Temperature Controller
-- continued from previous page
2000 VAC, 50 or 60 Hz for 1 min between different charging terminals
10 to 55 Hz, 10 m/s
300 m/s
Approx. 310 g
Front panel: NEMA 4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
EEPROM non-volatile memory (number of writes: 100,000)
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
Conforms to VDE0106/part 100 (Finger Protection) when the terminal cover is mounted.
Multiple points
RS-485 (two-wire, half duplex)/RS-232C
Start-stop synchronization
1,200/2,400/4,800/9,600/19,200 bps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSMAC WAY
Block check character (BCC): with CompoWay/F
Not available
RS-485/RS-232C
Not available
40 bytes
E54-CT1
50 amps
1,000 VAC (for 1 min)
50 Hz, 98 m/s
Approx. 11.5 g
Single-phase 50 A AC
0.1 to 49.9 A (in units of 0.1 A) (See Note 1)
190 ms (See Note 2)
----
2
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
E5AN
2
(10G)
2
for 2 hours each in X, Y and Z directions
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2:
ENV50140:
ENV50141:
EN61000-4-4:
Mounting bracket: Approx. 100 g
E54-CT3
120 amps (See Note 1)
Approx. 50 g
Armature: 2; Plug: 2
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
2
)

Related parts for E5AN-R3MT-500-N AC100-240