H3AM-NS-B300 Omron, H3AM-NS-B300 Datasheet

Electronic Analog Timer

H3AM-NS-B300

Manufacturer Part Number
H3AM-NS-B300
Description
Electronic Analog Timer
Manufacturer
Omron
Datasheet

Specifications of H3AM-NS-B300

Time Range
1sec To 60 Hr
Power Consumption
9VA
Reset Time
0.5s
Supply Voltage Ac, Min
100V
External Width
96mm
External Depth
85mm
Height
96mm
Supply Voltage Ac, Max
240V
Carry Current
5A
Approval Bodies
CSA / UL
Operating Temperature Max
55°C
Large Setting Dial and Moving Pointers
Ideal for Easy Operation and Monitoring
Ordering Information
1. Resetting System
100 to 240 VAC
Waterproof Packing
H3AM - NS
Rated supply
Model Number Legend
Accessory
Incorporating an easy-to-see large setting dial with
moving pointers.
Wide time-setting range of 0.2 s to 60 h (available
through three time-range model types)
Wide AC power supply range (100 to 240 VAC)
IP65 watertight and dust-tight front panel.
Approved by UL and CSA.
Conforms to IEC61812-1 (VDE0435/P2021)
Conforms to IEC60664-1 (VDE0110) 4KV/2
Conforms to EMC standards.
Six-language instruction manual provided.
Programmable contact enables the building of a
self-holding relay circuit as well as built-in
instantaneous contact. (-NS)
Memory retention (-NSR)
Finger protection terminal block
High immunity to inverter noise
Enables easy sequence checks through instanta-
neous outputs for a zero set value at any time range
a ed supp y
voltage
Mechatronic Analog Timer
None:Self-resetting
R:
lt
Item
Electric resetting
1
Self-resetting
Electric
resetting
-
Resetting
system
2
ese
-
t
3
g
Y92S-35
DPDT contact output
(Time-limit output SPDT and
switchable SPDT
(time-limit
DPDT contact output
(Time-limit output SPDT and
instantaneous output SPDT)
2. Time Range
Model
A: 0.5 s to 30 h
B: 1 s to 60 h
C: 0.2 s to 12 h
Control output
Co
instantaneous))
o ou pu
30 min, 3 h, 30 h)
H3AM-NS-A
H3AM-NSR-A
0.5 s to 30 h
(30 s, 3 min,
3. Accessory
None:
300:
H3AM-NS-B
H3AM-NSR-B
1 s to 60 h (60 s,
6 min, 60 min, 6
Time range
h, 60 h)
Without accessory
Waterproof Packing
(Y92S-35) provided
H3AM
R C
H3AM-NS-C
H3AM-NSR-C
12 min, 120 min,
0.2 s to 12 h
(12 s, 120 s
12 h)
1

Related parts for H3AM-NS-B300

H3AM-NS-B300 Summary of contents

Page 1

... VAC Self-resetting DPDT contact output (Time-limit output SPDT and switchable SPDT (time-limit Electric DPDT contact output resetting (Time-limit output SPDT and instantaneous output SPDT) Model Number Legend H3AM - Resetting System None:Self-resetting R: Electric resetting Accessory Item Waterproof Packing Y92S-35 ...

Page 2

... Contact output 250 VAC, resistive load (cos = 1) Ambient temperature Operating: – (with no icing) Storage: Ambient humidity Operating: 35% to 85% 2 Set time unit min 0 0. min 0 min 2 to 120 s 0 min 0 264 VAC VAC – (with no icing) H3AM 10 min h (hour (hour) 0 min 0. 0 min 0 120 min 0 --- ...

Page 3

... Enclosure rating IP65 (front panel only) (see note) IP20 (terminal section) Weight Approx. 350 g Note: A separately sold waterproof packing (Y92S-35) is necessary to ensure IP65 waterproofing between the Timer and installation panel. The H3AM-NSj-j-300 model with waterproof packing is available. 2 (approx. 30G (approx. 15G) (100 m/s (approx ...

Page 4

... Nomenclature Moving Pointer (green): Displays remaining time. Power Indicator Instantaneous or Time-limit Output Selector for R2 Relay: Default setting is time-limit output (Illustrated Model: H3AM-jjj-C) 4 Setting pointer (orange) Displays set value. Output Indicator Time Unit Indicator Time Unit Selector Applicable Time Unit Applicable time unit ...

Page 5

... H3AM-NSR Rt’ Power supply (1-2) Reset (9-10) Time-limit contact NC (3-4) Time-limit contact NO (3-5) Instantaneous contact NC (7-8) Instantaneous contact NO (6-8) Power indicator Output indicator Note: “ Rt’ ” indicates reset input time and “t” indicates set time. Rt’ H3AM 5 ...

Page 6

... Internal Connections and Terminal Arrangement H3AM-NS Power supply * (See note) Note: The R2 relay can be set to either instantaneous or time-limit contact using the switch located on the bottom of the Timer (H3AM-NS models). 6 77.5 dia. 27.5 dia. Note: Tightening torque for panel mounting is as follows: ...

Page 7

... Precautions for VDE Conformance The H3AM as a built-in timer conforms to VDE0435/P2021 provided that the following conditions are satisfied: The output section of the H3AM is provided only with basic isolation. To ensure reinforced isolation required by the VDE standards, pro- vide supplementary basic isolation on the load side connected to the output ...

Page 8

... Cat. No. L095-E1-1 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Devices and Components Division Supervisory Control Devices Division 28th Fl., Crystal Tower Bldg. 1-2-27, Shiromi, Chuo-ku, Osaka 540-6028 Japan Phone: (81)6-949-6014 Fax: (81)6-949-6069 8 H3AM Printed in Japan 0998-2M (0298) ...