AD18T OPTO 22, AD18T Datasheet

I/O Module

AD18T

Manufacturer Part Number
AD18T
Description
I/O Module
Manufacturer
OPTO 22
Type
Inputr
Datasheets

Specifications of AD18T

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Signal Input Type
Thermocouple
No. Of Outputs
1
Resolution
12 Bits
No. Of Analog Inputs
1
Connection To Host
Backplane
Current, Input
30 mA
Input
-200 to +224 °C
Input Type
Analog
Input, Range
-200 to +224 DegC
Mounting Type
PCB
Primary Type
Data Acquisition
Special Features
Optical Isolation, Thermocouple Input
Standards
UL, CSA, CE Certified
Temperature, Operating
0 to +70 °C
Time, Response
8.5 ms (5% of Scale Change), 165 ms (63% of Scale Change)
Voltage, Isolation
4000 VAC
Voltage, Supply
± 15 VDC
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
DATA SHEET
Form 439-040728
Description
of optically isolated temperature-to-digital conversion. The modules
offer wide nominal input and special over/under range capabilities.
The 'T' module also includes 4000 Vrms transient channel-to-
channel isolation which eliminates any ground loop problems.
Modules plug into a Classic standard analog I/O rack and are
secured by a captive screw.
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Features
* For 'T' models only.
** Accuracy figure requires use of gain and offset commands.
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: support@opto22.com
• Rugged Packaging
• 4000 Vrms Transient Isolation
• 12-bit Resolution
• Factory Calibrated, No User Adjustments
• Operating Temperature: 0° to 70° C
• "T" Models Offer Channel-to-Channel Isolation
The thermocouple analog modules provide a single channel
AD5
AD5T
AD8
AD8T
AD17T
AD18T
AD19T
THERMOCOUPLE INPUTS
Number
Part
I/O MODULES
K Thermocouple Input
K Thermocouple Input, Isolated
R or S Thermocouple Input, Isolated
E Thermocouple Input, Isolated
J Thermocouple Input
J Thermocouple Input, Isolated
T Thermocouple Input , Isolated
Description
STANDARD
page 1/4

Related parts for AD18T

AD18T Summary of contents

Page 1

... Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: support@opto22.com I/O MODULES STANDARD THERMOCOUPLE INPUTS Part Description Number AD5 J Thermocouple Input AD5T J Thermocouple Input, Isolated AD8 K Thermocouple Input AD8T K Thermocouple Input, Isolated AD17T Thermocouple Input, Isolated AD18T T Thermocouple Input , Isolated AD19T E Thermocouple Input, Isolated page 1/4 ...

Page 2

... 700° C) ± 3° C (-100 to 924° C) ± 1° C ± 1° +15 VDC +15 VDC -15 VDC -15 VDC AD17T AD18T S T 0° to 1034° -200° to 224° 32° to 1893° -328° to 435° -50° to 1768° -200° to 400° ...

Page 3

... THERMOCOUPLE INPUTS 4000 Vrms (Transient) 4000 Vrms Yes Yes 5% of scale change in 8.5 ms 63% of scale change in 165 ms 0° to 70°C - 25° to 85°C 12 bits Model AD5/AD5T AD8/AD8T AD17T AD18T AD19T AD17T I/O MODULES STANDARD page 3/4 Polarity/Color T/C Type + - J WHITE RED ...

Page 4

... Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com Inside Sales: (800) 321-OPTO • ...