OAC15A OPTO 22, OAC15A Datasheet - Page 2

I/O Module

OAC15A

Manufacturer Part Number
OAC15A
Description
I/O Module
Manufacturer
OPTO 22
Type
Outputr
Datasheets

Specifications of OAC15A

Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
1
Supply Voltage Min
9VDC
Signal Input Type
9 To 16VDC
Output Current
3A
Supply Voltage Max
16VDC
Count Input Frequency
65Hz
Contact Configuration
SPST-NO
Connection To Host
Backplane
Current, Input
15 mA
Current, Leakage
2.5 mA (RMS) (Off-State) @ 120 VAC
Dimensions
43.2mmL×15.2mmW×31.8mmH
Module Type
Digital
Number Of Channels
1
Output
24 to 280 VAC
Output Type
Analog
Output, Range
24 to 280 VAC
Primary Type
Data Acquisition
Resistance, Insulation
100 Megohms (Min.) @ 500 VDC
Special Features
Optical Isolation
Standards
UL Listed
Temperature, Operating
-30 to +70 °C
Time, Turn-off
1⁄2 Cycle (Max.) @ 0 V
Time, Turn-on
1⁄2 Cycle (Max.) @ 0 V
Voltage, Isolation
4000 VAC
Voltage, Operating
24 to 280 VAC
Voltage, Supply
15 VDC
No. Of Analog Inputs
1
No. Of Outputs
1
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
PAGE
2
Specifications
General
Module Specifications
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2006–2009 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
One Cycle Surge
Peak Repetitive Voltage
Operating Ambient Temperature
Isolation, Input-to-Output (Transient)
Minimum Load Current
Operating Frequency
Turn-on Time
Turn-off Time
DV/DT - Off-State
DV/DT - Commutating
Output Voltage Drop Maximum Peak
Off-State Leakage
@ Nominal Voltage - 60 Hz
Line Voltage - Nominal
Operating Voltage Range
Current Rating
UL Motor Load Rating
Logic Voltage - Nominal
Logic Voltage Range (Vcc)**
Logic Pickup Voltage*
Logic Dropout Voltage
Logic Input Current-@ Normal Logic
Voltage (I
Control Resistance
(R
* Not UL approved
** Module only
@ 45 °C Ambient
@ 70 °C Ambient
c
in schematic diagram)
out
in schematic diagram)
Units
VAC
VAC
amps
amps
amps
VDC
VDC
VDC
VDC
mA
Ohms
OAC5
120
12–140
3
2
1.5
5
2.5
2.5
1
12
220
80 amps peak
500 Volts
-30 to 70 °C
4,000 Vrms
20 milliamps
25–65 Hz
1/2 cycle maximum-zero voltage
1/2 cycle maximum-zero current
200 volts/microseconds
Snubbed for rated 0.5 power factor load
1.6 volts
5 milliamps rms
2.5 milliamps rms for OAC5A OAC15A,
and OAC24A @120 VAC
8
OAC5A
240
24–280
3
2
1.5
5
2.5
2.5
1
12
220
8
OAC5H
240
24–280
4
2
5
2.5
12
220
-- *
2.5
1
8
Standard AC Output Modules
OAC5A5
(NC)
120/240
24–280
3
2
1.5
5
2.5
2.5
1
12
220
8
OAC15
120
12–140
3
2
1.5
15
9
9
1
15
1K
16
OAC15A
240
24–280
3
2
1.5
15
9
9
1
15
1K
16
OAC24
120
12–140
3
2
1.5
24
18
18
1
18
2.2K
32
OAC24A
240
24–280
3
2
1.5
24
18
18
1
18
2.2K
32
OAC24H
240
24–280
4
2
-- *
24
18
18
1
18
2.2K
32

Related parts for OAC15A