SNAP-AIPM OPTO 22, SNAP-AIPM Datasheet - Page 7

Power Monitoring Module

SNAP-AIPM

Manufacturer Part Number
SNAP-AIPM
Description
Power Monitoring Module
Manufacturer
OPTO 22
Type
Inputr
Datasheets

Specifications of SNAP-AIPM

Accessory Type
Single-phase Power Monitoring Module
Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Signal Input Type
85 To 250V And 0 To 10A RMS
Brand/series
SNAP Series
Connection To Host
Backplane
Current, Input
100 mA
Current, Supply
0 to 10 A
Dimensions
82.55mmL×18.29mmW×90.17mmH
Input
85 to 250/0 to 10 VAC/AAC
Input Resolution
10 mV
Input Type
Analog
Input, Range
85 to 250/0 to 10 VAC/AAC
Mounting Type
PCB
Number Of Channels
2
Number Of Inputs
2 Channels
Primary Type
Control
Resistance, Input
1 Megohms
Special Features
Transformer Isolation, Optical Isolation
Standards
UL, CSA, CE Certified
Temperature, Operating
0 to +70 °C
Voltage, Isolation
4000 V
Voltage, Supply
5 VDC
No. Of Analog Inputs
4
Resolution
10mV, 400uA
Rohs Compliant
No
For Use With
Snap I/O Modules
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
SNAP Power Monitoring Modules
Scaling Example 1: SNAP-AIPM without PT
Leave Actual values at their defaults for all points, and leave
Lower Scaled values at 0. Calculate Upper Scaled values for
points as follows:
Point 0: Always 250 volts for line voltage between 85 and 250
VAC. (For line voltage over 250 V, use Example 2.)
Point 1: 10* (CT primary / CT secondary)
Point 2: Upper Scaled for pt 0 (voltage)* Upper Scaled for pt 1
(current)
Point 3: Upper Scaled for voltage * Upper Scaled for current
Example
Voltage: 240 VAC (no potential transformer required)
Current: 180 amps (requires CT primary of 200).
CT has a secondary of 5 A; the module accommodates 10 A.
So to calculate point 1: 10 * (200/5) = 400
...points 2 and 3: 250 * 400 = 100,000
© 2006–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Units
Lower
Upper
Units
Lower
Upper
VAC/VDC VAC/VDC
Actual
Actual
2500
250
W
0
0
Voltage
Point 0
Point 2
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
Watts
100,000
Scaled
Scaled
250
W
0
0
Actual
Actual
2500
VA
10
A
0
0
Volt Amps
Current
Point 1
Point 3
100,000
Scaled
Scaled
400
VA
A
0
0
Scaling Example 2: SNAP-AIPM with PT
For line voltage higher than 250 VAC, a step-down
potential transformer (PT) must be used.
Leave Actual values at their defaults for all points, and leave
Lower Scaled at 0. Calculate Upper Scaled values for points as
follows:
Point 0: 250 * PT ratio
Point 1: 10* (CT primary / CT secondary)
Point 2: Upper Scaled for pt 0 (voltage)* Upper Scaled for pt 1
(current)
Point 3: Upper Scaled for voltage * Upper Scaled for current
Example
Voltage: 277 VAC (requires potential transformer).
PT ratio is 2:1
Current: 350 amps (Requires CT primary of 400. CT has a
secondary of 5 A; the module accommodates 10 A.
So to calculate point 0: 250 * 2 = 500
...point 1: 10 * (400/5) = 800
...points 2 and 3: 500 * 800 = 400,000
Units
Lower
Upper
Units
Lower
Upper
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
VAC/VDC VAC/VDC
Actual
Actual
2500
250
Point 2 (6, 10)
W
Point 0 (4, 8)
0
0
Voltage
Watts
400,000
Scaled
Scaled
500
W
0
0
Actual
Actual
2500
Point 3 (7, 11)
Point 1 (5, 9)
VA
10
A
0
0
Volt Amps
Current
400,000
Scaled
Scaled
800
VA
A
0
0
PAGE
7