FPG-COM1-A PANASONIC EW, FPG-COM1-A Datasheet - Page 15

High-speed Micro PLC - FP Sigma Series, 1 RS232C Communication Cassette

FPG-COM1-A

Manufacturer Part Number
FPG-COM1-A
Description
High-speed Micro PLC - FP Sigma Series, 1 RS232C Communication Cassette
Manufacturer
PANASONIC EW
Datasheet

Specifications of FPG-COM1-A

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
FP Web-Server
Program/Operate the FPΣ (Sigma) using a LAN or WAN network
The multifunctional FP Web-Server provides users with the option of connecting the FPΣ (Sigma) or any other
FP Series PLC to the Internet/Intranet thus enabling bi-directional communication. No changes to the PLC
programs are necessary. Simply assign an IP address to the FP Web-Server and connect the PLC to the
FP Web-Server via the serial RS232C interface. A standard browser e.g. MS Internet Explorer or Netscape
Navigator can be used for access at the PC.
-PLC data represented as HTML (or XML) pages
-Access via standard Internet browser
-PLC data handling via HTML and Java Applet
-Optional: Password protection, IP-Lok security
-Ethernet <–> RS232C conversion (MEWTOCOL)
-Transparent RS232C data tunneling via Ethernet
-Programming and visualisation via TCP or UDP
-Communication via standard industrial Ethernet
protocol (server and client)
Protocols
Number of browsers
Number of emails
Number of email addresses
Number of PLC per unit
IP address
Security
Operating power
Dimensions
LEDs
Flash memory
Standards fulfilled
Highlights
Web-Server:
RS232C device server:
Modbus- TCP protocol:
The FP Web-Server´s 3 interfaces
– connects to the Ethernet at 10 Mbit/s
– connects to the FPΣ (Sigma) at 1200 to 115.2 kbit/s
– connects to a modem (PPP)
TCP/IP, UDP/IP, SMTP, PPP, NTP, FTP, TELNET, HTTP, MEWTOCOL-COM
Up to 64 browsers can be connected to one FP Web-Server
4 predefined in FP Web Flash memory
1 programmable in PLC DT memory as ASCII
4 predefined in FP Web flash memory, 1000 addresses in PLC DT memory,
assuming an average of 32 characters are used per email address and that an
FP0-T32CP is used, which has 16k word memory
Two PLCs can be connected
3-pin port (port number: 9094)
DB8 port (port number: 9095)
DHCP or manually set by software
Password and DIP switch
24VDC, 75mA (max.)
25 x 90 x 60mm (W x H x D)
Power, COM Ethernet connection, COM data exchange
512KBytes
CE, UL, cUL
10BaseT (RJ45, twisted pair)
RS232C (screw terminal)
RS232C (SUB-D 9 male)
-PLC can send emails
-Email via LAN email server or Internet dial-up
-PLC-defined or pre-stored mail text
-PLC data array as attachment to an email
-FP Web-Server can be dialed up via modem
-One remote gateway for multiple FP Web-Servers in
-PLC real-time clock update via NTP server
a local Ethernet network
02/2006
Email:
Modem/Ethernet gateway:
Network time server synchronisation:
15

Related parts for FPG-COM1-A