G4IDC5Q OPTO 22, G4IDC5Q Datasheet

no-image

G4IDC5Q

Manufacturer Part Number
G4IDC5Q
Description
I/O Module
Manufacturer
OPTO 22
Datasheet

Specifications of G4IDC5Q

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Signal Input Type
4 To 16VDC
Supply Voltage
16V
Count Input Frequency
12.5kHz
No. Of Analog Inputs
2
Operating Temperature Min
-30°C
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
I/O MODULES
G4
QUADRATURE
DATA SHEET
page 1/4
Form 548-040728
Part
Description
Numbers
Description
G4IDC5Q
G4 DC Input, 4-16 VDC, 5 VDC Logic, 2-Channel Quadrature
The G4IDC5Q quadrature input module pair is designed to allow a digital mistic 200 multi-function I/O Brick to resolve positional
information from quadrature encoder devices. The module will output a pulse to the Brick each quadrature state changes. The
Brick will count the module outputs and keep track of direction of rotation.
Features
• 4000 Vrms transient optical isolation
• Built-in LED status indicators
• 4 times encoder resolution
• Installs on mistic 200 bricks
• Input signals in 4-16 VDC range
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: support@opto22.com

Related parts for G4IDC5Q

G4IDC5Q Summary of contents

Page 1

... Form 548-040728 Description The G4IDC5Q quadrature input module pair is designed to allow a digital mistic 200 multi-function I/O Brick to resolve positional information from quadrature encoder devices. The module will output a pulse to the Brick each quadrature state changes. The Brick will count the module outputs and keep track of direction of rotation. ...

Page 2

... The G4IDC5Q is actually a pair of modules, one of which is labeled “A”, the other “B”. When the signal into the module A leads the signal into module B, the output will be on module A. When the signal into module B leads the signal into module A, the output will be on module B ...

Page 3

... Connection Diagram Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • Email: support@opto22.com © ...

Page 4

... Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (951) 695-3000 • (800) 321-OPTO • Fax: (951) 695-3095 • www.opto22.com Inside Sales: (800) 321-OPTO • ...

Related keywords