4380-2001-1 EUROTHERM CONTROLS, 4380-2001-1 Datasheet - Page 4

Isolation Amplifier

4380-2001-1

Manufacturer Part Number
4380-2001-1
Description
Isolation Amplifier
Manufacturer
EUROTHERM CONTROLS
Datasheets

Specifications of 4380-2001-1

Width
2.85"
Output Accuracy
± 0.35% Of FS (20mV / 2mA)
± 0.1% Of Fs (20mv / 2ma)
Signal Input Type
Configuration Setup
DIP Switch
Supply Voltage Max
240VAC
Iso-amp Mounting Type
DIN Rail
Signal Input Type
Selectable Current Or Voltage
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
Specifications
Input
Output
Eurotherm Controls
741-F Miller Drive
Leesburg, VA 20175-8993
703-443-0000
info@eurotherm.com
actionio.com
Mounting
All Action Paks feature plug-in installation.
Model AP4380 uses an 8-pin base, either
molded socket
M008 or DIN socket MD08.
Ordering Information
Specify:
1. Model: AP4380-2000 or AP4380-2001
2. Option: U, see text
3. Line Power, see specifications
4. Factory calibration (C620): Specify input
Pin Connections
1 Power (Hot)
2 Not Internally Connected
3 Power (Neu)
4 Spare Termination
5 Input (+)
6 Input (-)
7 Output (+)
8 Output (-)
DC Power: PIN 1 = (+); PIN 3 = (-)
range, output range and power.
(All power supplies are transformer-
isolated from the internal circuitry.)
Voltage Input (field configurable)
Voltage Output
Action Instruments
Full Scale Range:
Impedance: >100K Ohms
Current Input (field configurable)
Common Mode (Input toGround):
Zero Turn-Up:
Span Turn-Down:
Output: 0-5V, 0-10V
Drive: 10mA, max (1K Ohms min. @ 10V)
-2000: 10mV to 100V
-2001: 10mV to 200V
Overvoltage:
Intermittent, 400Vrms
Continous, 264 Vrms
Full Scale Range: 1mA to 100mA
Impedance: 20 Ohms, typical
Overcurrent: 170mA RMS, max
Overvoltage: 60VDC
1500VDC, max
50% of full scale range
50% of full scale range
Barber-Colman
LED Indication (green)
Accuracy (Including Linearity Hysteresis)
Response Time (10-90%)
Stability (Temp)
Common Mode Rejection
Isolation
Dimensions
Dimensions are in millimeters (inches)
Current Output
Input Range
<20mV/2mA: ±0.35% of full scale, typical,
>20mV/2mA: ±0.1% of full scale, typical,
200 mSec., typical
±0.025% of full scale/°C, typical,
±0.05%/°C, max.
DC to 60Hz: 120dB
500 VDC between input, output and power
Output: 0-1mA, 4-20mA
Compliance:
>110% input: 8Hz flash
<0% input: 4Hz flash
0.5%, max
0.2%, max
0-1mA: 10V, max. (10K Ohms, max)
4-20mA: 20V, max. (1K Ohms, max)
Eurotherm Chessell
721-0545-00-M 09/04 Copyright© Eurotherm, Inc 2004
Factory Assistance
For additional information on calibration, operation and
installation contact our Technical Services Group:
actionsupport@eurotherm.com
703-669-1318
ESD Susceptibility
Humidity (Non-Condensing)
Temperature Range
Power
Weight
Agency Approvals
Meets IEC 801-2, Level 2 (4KV)
Operating: 15 to 95% (@ 45°C)
Soak: 90% for 24 hours (@ 45°C)
Operating: -15 to 60°C (5 to 140°F)
Storage: -25 to 70°C (-13 to 158°F)
Consumption: 3W typical, 5W max
Standard: selectable 120/240VAC, ±10%,
Optional: 9 to 30VDC, inverter isolated
AP4380 .60lbs
CSA certified per standard C22.2, No. M1982.
UL recognized per standard UL508.
50-60Hz
M008 (Track/Surface)
MD08 (DIN Rail)
Eurotherm Controls

Related parts for 4380-2001-1