MCR-VDC-UI-B-DC Phoenix Contact, MCR-VDC-UI-B-DC Datasheet

no-image

MCR-VDC-UI-B-DC

Manufacturer Part Number
MCR-VDC-UI-B-DC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-VDC-UI-B-DC

Input Type
Voltage
Output Type
Analogue Signal
No. Of Output Channels
2
Accuracy
± 1%
Supply Voltage Range
18.5VDC To 30.2VDC
Approval Bodies
CE, UL Recognised
External Depth
114.5mm
External Length /
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
MCR-VDC-UI-B-DC
Voltage Transducer for DC Voltages
INTERFACE
Data Sheet
100260_en_01
1
The MCR voltage transducer measures DC voltages in
several signal ranges from 0 ... ±20 V DC to 0 ... ±660 V DC
and converts them to standardized analog signals.
DC voltages can be processed with both positive and
negative polarity.
The input voltage ranges listed at input terminal blocks 1 to
7 can be varied by ±20% using a calibration potentiometer.
The voltage transducer is calibrated by default to 0 ... ±24 V
input and 0 ... ±10 V output and is ready for operation when
delivered. To use the device with other input or output
variables, carry out a ZERO/SPAN adjustment using the
potentiometer on the front.
1.1
3-way electrical isolation
True r.m.s. value measurement
Adjustable voltage ranges
ZERO/SPAN adjustment ±20%
Description
Features
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
© PHOENIX CONTACT - 11/2007
1.2
The input circuit divides the DC voltage at terminal blocks 1
to 7. The resulting signal is electrically isolated and
transmitted to the output circuit and is available at the output
as a standardized analog signal.
1.3
When using the voltage transducer, please ensure that the
potential difference between terminal blocks 1 to 7 to
ground potential PE or terminal block 8 to ground potential
PE U does not exceed ±660 V (this condition applies to
circuits that are not grounded).
In DC voltage networks, this potential difference must not
exceed U = ±100 V (this condition applies to circuits that are
grounded).
When these conditions are met, safe isolation is ensured
between input, output, and supply.
Method of Operation
Field of Application

Related parts for MCR-VDC-UI-B-DC

MCR-VDC-UI-B-DC Summary of contents

Page 1

... MCR-VDC-UI-B-DC Voltage Transducer for DC Voltages INTERFACE Data Sheet 100260_en_01 1 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0 ... ± ... ±660 V DC and converts them to standardized analog signals. DC voltages can be processed with both positive and negative polarity. The input voltage ranges listed at input terminal blocks can be varied by ± ...

Page 2

... V DC (36 kΩ) ± (24 kΩ) ±660 V DC (not grounded) ±100 V DC (to ground) -10 V ... 10 V ±15 V > 10 kΩ < -20 mA ... 20 mA ±30 mA < 500 Ω < 18 ... 30 < True r.m.s. value measurement < 1% (of final value) < 0.015%/K ±20% ±20 IP20 MCR-VDC-UI-B-DC Pcs./Pck PHOENIX CONTACT ...

Page 3

... According to EN 50178 1.5 kV (50 Hz, 1 min.) II -25°C ... +50°C CE-compliant u EN 61000-4 air discharge EN 61000-4-3 10 V/m 10 V/m EN 61000-4-4 Input/output/supply: 2 kV/5 kHz Input/output: 2 kV/42 Ω EN 61000-4-5 Supply: 0.5 kV/2 Ω EN 61000-4-6 Input/output/supply 55011 Class A MCR-VDC-UI-B-DC 3 PHOENIX CONTACT ...

Page 4

... DIN rails according to EN 60715. Install the module in suitable housing to meet the requirements for the protection class. Screw Connection Insert the wires in the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block MCR-VDC-UI-B- ...

Page 5

... Close the housing again until it engages with a click Carry out a ZERO/SPAN adjustment each time the input or output range is changed ± 1 ± 2 ± Jumper/ Setting J1/setting 1 J1/setting 2 J1/setting 3 (default setting) MCR-VDC-UI-B-DC 54V HYBRID TV1 36V 24V PHOENIX J CONTACT 1 54V 2 36V 3 24V PHOENIX CONTACT 5 ...

Page 6

... Current output (0 … ±20 mA): I Final Value Adjustment (SPAN) Use the calibration device to specify the maximum voltage used within the input voltage range (see "Selecting the Input Voltage Range" on page 5). Set the output signal value (U OUT mA) using the SPAN potentiometer. OUT MCR-VDC-UI-B- OUT = 0 mA OUT = ...