06717 Simpson, 06717 Datasheet - Page 20

no-image

06717

Manufacturer Part Number
06717
Description
SIGNAL CONDITIONING,EXTERNAL PORTABLE AND SWITCHBOARD SHUNTS,SIGNAL CONDITIONING,SIGNAL CONDITIONING, OUTPUT CURRENT RATING 100 AMPERE,METERS,EXTERNAL PORTABLE AND SWITCHBOARD SHUNTS ,SIMPSON
Manufacturer
Simpson
Type
Current Shuntsr
Datasheets

Specifications of 06717

Rohs Compliant
NA
Current, Rating
100 A
Dimensions
6.00 in. L x 1.975 in. W x 1.60 in. H
Includes
5 Foot Leads
Resistance
0.065 Ohms
Screw Size
3⁄8-16, 10-32
Voltage, Output
100 mV
Equipment Type
Portable Shunt
Range
0 - 100
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Models & Parameters
Accessories - Three-Phase Current Transformer
A three-phase terminal style current transformer must be used with
GIMA® three phase meters.
The current transformer is equipped with terminals to permit easy con-
nection to the GIMA units. These terminals are #8-32 brass studs and
come with a flatwasher, lockwasher and a regular nut (leads are not
provided).
Ordering Information
Catalog Number
Phase Amps
Phase Volts
Line Volts
Per Phase PK
Per Phase kW
Per Phase kvar
Per Phase kVA
3 Phase PF
3 Phase kW
3 Phase kvar
3 Phase kVA
Frequency
KWh
Capacitive kvarh
Inductive kvarh
Total kvarh
Import kvarh
Current Demand
Voltage Demand
kW Demand
Peak Amps
Peak Phase Volts
Peak Current Demand
Peak Voltage Demand
Neutral Current
37026
37027
37028
37029
37030
Current Ratio
100:5
150:5
200:5
300:5
50:5
G100 G200
X
X
X
X
X
X
X
X
X
X
X
X
Accuracy @ 60Hz
± 3%
± 1%
± 1%
± 1%
± 1%
X
X
X
X
X
X
X
X
X
X
X
X
X
G300
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Burden VA @ 60 Hz
G400
10.0
2.0
2.0
4.0
5.0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Ordering Information
Mounting Requirements
Panels should be .04 to .16 inches (1mm to 4mm) thick with a
square cut-out of 3.62” x 3.62” (92mm x 92mm.) A minimum depth
of 2.83” (72mm) should be allowed behind the panel for the meter.
Remove the panel mounting clips and insert the meter into the cut-
out from the front of the panel. Push the meter home. Ensure the
screws in each panel mount clip are fully retracted and insert the
clips as shown in the diagram below. Tighten the screws to secure
the meter firmly in the panel.
Do not overtighten.
G
For other Voltage and Current Inputs, contact Simpson Electric Company
B B a a s s i i c c U U n n i i t t
100
200
300
400
1
2
3
4
1
0
1
2
P P o o w w e e r r
V V o o l l t t a a g g e e I I n n p p u u t t s s
B B a a s s i i c c U U n n i i t t
GIMA 100 Meter
GIMA 200 Meter
GIMA 300 Meter
GIMA 400 Meter
P P o o w w e e r r S S u u p p p p l l y y
115 VAC @ 45-65Hz
230 VAC @ 45-65 Hz
V V o o l l t t a a g g e e I I n n p p u u t t
120/208V
120/240V - Split Phase
277/480V
C C u u r r r r e e n n t t I I n n p p u u t t
O O t t h h e e r r
None
5 amp
63/110V
C C u u r r r r e e n n t t I I n n p p u u t t
O O t t h h e e r r

Related parts for 06717