CUB20000 Red Lion Controls, CUB20000 Datasheet - Page 2

no-image

CUB20000

Manufacturer Part Number
CUB20000
Description
CUB 2 MIN. ELEC. COUNTER
Manufacturer
Red Lion Controls
Datasheet

Specifications of CUB20000

Rohs Compliant
NA
Digit Height
0.56
Number Of Digits
3-1/2
APPLICATION FLEXIBILITY VIA RECONNECT OPTIONS
switch increments the counter. The low pass filter (1meg resistor and 4700 pf
cap) used with a Schmidt trigger circuit debounces mechanical switch signals.
The switch load is 14 µA (max. voltage drop 0.5 V) when ON. OFF-state
leakage current must be less than 2 µA.
operate at speeds up to 5 KHz when driven by bi-polar outputs or external
circuits having an output impedance of 3.3 KΩ or less. Input drive voltage
must be limited to 3.0 V maximum to avoid a charging current into the
batteries which can cause premature battery failure or leakage. CMOS and
TTL Logic outputs can be loaded with a resistor (R
a voltage divider can be used as shown for the PNP O.C. Transistor output.
LOW SPEED COUNT INPUT, 50 Hz MAX. [For 250 Hz see note in text]
HIGH SPEED COUNT INPUT, 5 KHz MAX.
RESET OPTIONS
Pulling the L.S. CNT. Input to Common with a mechanical or solid-state
Moving the white wire to the H.S. CNT. Input allows the CUB Counter to
L
) to limit drive voltage, or
2
terminal leads in the Input Connector Body. The connector body is polarized to
prevent incorrect insertion, and locked in place by the battery cover to avoid
accidental disengagement. Connectors are supplied with the 3 leads installed as
shown below. A spare blue lead is supplied in the hardware pack.
TO REMOVE TERMINAL, insert blade of a small screwdriver into slot of
WHEN INSERTING TERMINAL into connector body, make sure the lock
silver alloy relay contacts with wiping action are usually satisfactory for
generating count input signals. Motor starter contacts, tungsten contacts, and
brush-type contacts should NOT be used.
Note: By parallel connecting both H.S. CNT. and L.S. CNT. inputs, count
Note: The PSMA Power Supply and Interface Module used for powering RLC
front panel Reset button. When the front panel Reset button is to be de-
activated, remove the yellow wire from the RST. EN. Input.
inserted in the REM. RST. Input. Pulling this input low causes the counter to
reset. The REM. RST. can be pulled low by either a mechanical switch or
solid-state transistor switch. Switch load and leakage are the same as for L.S.
CNT. Input above.
Note: The RC protection circuit on the REM. RST. Input causes a delay of
Selection of desired operating modes is easily done by adding or moving
connector body, and gently push in to disengage lock pawl. Pull terminal out.
pawl is toward the slot in the body. Push terminal in until lock pawl snaps
into slot.
Reed switches, mercury wetted contacts, snap action limit switches, and
speed can be increased to 250 Hz if de-bounce is not needed.
sensors with CUB Counters, has proper interface output for direct drive to
H.S. CNT.
Connecting the RST. EN. (Reset Enable) Input to Common activates the
When Remote Reset is required, the blue wire in the hardware pack is
approximately 6 msec in Reset response.
TTL OR CMOS
OUTPUT
INPUT PULSE EXCURSION LIMITS
V
IN
(High) = +2.7 V min. +3.3 V max.
V
IL
(Low) = +0.5 V max.
PNP O.C. TRANSISTOR
OR BI-POLAR OUTPUT
O.C. TRANSISTOR
NPN