TEMPERATURE CONTROLLER
Manufacturer
Omron
Series
E5GNr
Type
Temperature Controller, Digitalr
Datasheet

Specifications of E5GN-R1P AC100-240

Input Type
RTD
Controller Type
On/Off or Proportional (PID)
Temperature Range
Selectable, Varies By Input Type
Output Type
Relay
Supply Voltage
100 ~ 240VAC
Size
48mm W x 24mm H (1/32 DIN)
Features
NEMA 4X, IP66
Display Type
4 Digit (2)
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Communications
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E5GN-R1PAC100-240
E5GNR1PAC100240
■ Characteristics
Note 1. The indication of K thermocouples in the –200 to 1300 C range, and T and N thermocouples at a temperature of –100 C or less, and U
Indication accuracy
Temperature variation influence (See note
2.)
Voltage variation influence (See note 2.)
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
Degree of protection
Memory protection
EMC
Approved standards
Compliant standards
2. Ambient temperature: –10 C to 23 C to 55 C
and L thermocouples at any temperature is 2 C 1 digit maximum. The indication of B thermocouples at a temperature of 400 C or less
is unrestricted.
The indication of R and S thermocouples at a temperature of 200 C or less is 3 C 1 digit maximum.
Voltage range:
–15% to 10% of rated voltage
Thermocouple:
( 0.5% of indicated value or 1 C, whichever greater) 1 digit max. (See note 1.)
Platinum resistance thermometer:
( 0.5% of indicated value or 1 C, whichever greater) 1 digit max.
Analog input: 0.5% FS 1 digit max.
Thermocouple input (R, S, B):
( 1% of PV or 10 C, whichever greater) 1 digit max.
Other thermocouple input:
( 1% of PV or 4 C, whichever greater) 1 digit max.
K thermocouple at –100°C max.: 10 C max.
Platinum resistance thermometer: ( 1% of PV or 2 C, whichever greater) 1 digit max.
Analog input: ( 1%FS) 1 digit max.
0.1 to 999.9 EU (in units of 0.1 EU)
0.1 to 999.9 EU (in units of 0.1 EU)
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
–1999 to 9999 (decimal point position depends on input type)
500 ms
20 M min. (at 500 VDC megger)
2000 VAC, 50 or 60 Hz for 1 min (between different charging terminals)
10 to 55 Hz, 10 m/s
300 m/s
Approx. 90 g
Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
EEPROM (non-volatile memory) (number of writes: 100,000)
ESD Immunity:
Radiated Electromagnetic Field Immunity: IEC 61000-4-3
Burst Immunity:
Surge Immunity:
Conducted Disturbance Immunity: IEC 61000-4-6:
Voltage Dip/Interrupting Immunity: IEC 61000-4-11
Radiated Emission:
Conducted Emission:
UL 61010C-1 (Listing)
CSA C22.2 No. 1010.1 (Evaluated by UL.)
EN 61010-1:
IEC 61010-1:
2
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
2
for 2 hours each in X, Y and Z directions
Digital Temperature Controllers
IEC 61000-4-2:
4 kV: Contact discharge
8 kV: Air discharge
10 V/m (80 MHz to 1 GHz amplitude modulated)
IEC 61000-4-4:
2 kV: Power lines
1 kV: I/O signal lines
IEC 61000-4-5:
1 kV: Normal mode (power lines and output lines)
2 kV: Common mode (power lines and output lines)
3 V: (0.16 to 80 MHz)
0.5 cycle, 100% (rated voltage)
EN 61326 Class A
EN 61326 Class A
2001
2001