MTL5511 MTL SURGE TECHNOLOGIES, MTL5511 Datasheet

no-image

MTL5511

Manufacturer Part Number
MTL5511
Description
ISOLATED BARRIER, DIG I/P
Manufacturer
MTL SURGE TECHNOLOGIES
Datasheet

Specifications of MTL5511

Input Type
Proximity Detectors
Output Type
Relay
Approval Bodies
ATEX
External Depth
123.6mm
External Length / Height
109.8mm
External Width
15.8mm
Isolation Input
Isolated
Mounting Type
DIN Rail
Svhc
No SVHC (15-Dec-2010)
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
The MTL5511 enables a safe-area load to be controlled by a switch
or proximity detector located in a hazardous-area. When selected,
open or short circuit conditions in the field wiring are detected by
the line-fault-detect (LFD) facility and also indicated on the top of the
module. Phase reversal for the channel is selected by a switch on
the side of the module and output is provided by changeover relay
contacts.
SPECIFICATION
See also common specification
Number of channels
Location of switches
Location of proximity detector
Hazardous-area inputs
Voltage applied to sensor
Input/output characteristics
Line fault detection (LFD) (when selected)
Safe-area output
Relay characteristics
MTL5511 SWITCH/
PROXIMITY DETECTOR
INTERFACE
single channel, with line fault detection
One
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
7 to 9V dc from 1kΩ ±10%
Normal phase
Hysteresis: 200μA (650Ω) nominal
User-selectable via switches on the side of the unit. A line fault is
indicated by an LED. The channel output relay is de-energised if
an input line fault is detected.
Open-circuit alarm on if Iin < 50μA
Open-circuit alarm off if Iin > 250μA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact
input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Single pole relay with changeover contacts
Note: reactive loads must be adequately suppressed
Response time:
Contact rating:
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
EUROPE (EMEA)
AMERICAS
ASIA PACIFIC
E-mail: enquiry@mtl-inst.com
10ms maximum
250V ac, 2A, cosØ >0.7
40V dc, 2A, resistive load
Tel: +44 (0)1582 723633
Tel: +1 281 571 8065
Tel: +65 6 487 7887
Web site: www.mtl-inst.com
Fax: +44 (0)1582 422283
Fax: +1 281 571 8069
Fax: +65 6 487 7997
* Signal plug HAZ1-3 is required for access to this function
LED indicators
Maximum current consumption
Power dissipation within unit
Safety description (each channel)
The given data is only intended as a product description and should not be re-
garded as a legal warranty of properties or guarantee. In the interest of further
technical developments, we reserve the right to make design changes.
Hazardous area
Terminal
Green: power indication
Yellow: channel status, on when output is energised
Red:
25mA at 24V
0.6W at 24V
V
o
=10.5V I
10
11
12
13
14
1
2
3
W
W
LFD indication, on when line fault is detected
o
=14mA P
Function
Input –ve
Input +ve
To earth leakage detector*
Output normally-closed contact
Common
Output normally-open contact
Supply –ve
Supply +ve
o
=37mW U
Safe area
m
= 253V rms or dc
EPS5511-2
Jan 2009

Related parts for MTL5511

MTL5511 Summary of contents

Page 1

... PROXIMITY DETECTOR INTERFACE single channel, with line fault detection The MTL5511 enables a safe-area load to be controlled by a switch or proximity detector located in a hazardous-area. When selected, open or short circuit conditions in the field wiring are detected by the line-fault-detect (LFD) facility and also indicated on the top of the module ...