P4800001 Red Lion Controls, P4800001 Datasheet - Page 3

no-image

P4800001

Manufacturer Part Number
P4800001
Description
W/Analog Output
Manufacturer
Red Lion Controls
Type
Process Controllerr
Datasheet

Specifications of P4800001

Brand/series
P48 Series
Dimensions
1.95 × 1.95 × 4.17 In.
Enclosure Rating
IP65
Input Type
0-10 VDC / 4-20 mA
Mounting Type
Panel
Number Of Inputs
1
Number Of Outputs
1
Output Type
Analog
Primary Type
Controller
Rating
IP65
Special Features
Programmable User Input
Termination
Screw
Voltage, Supply
85-250 VAC
16. ISOLATION BREAKDOWN RATINGS:
17. CERTIFICATIONS AND COMPLIANCES:
18. CONNECTION: Wire clamping screw terminals
19. CONSTRUCTION: Black plastic alloy case and collar style panel latch.
20. WEIGHT: 0.38 lbs (0.17 kgs)
BASIC OPERATION
process value, then calculating a control output power value by use of a
modified PID control algorithm. The unit controls the system with the new
output power value to keep the process at setpoint. The PID control algorithm
incorporates features which provide for high control accuracy and low
overshoot from process disturbances.
AC line with respect to all Inputs and outputs: 250 V working (2300 V for
Main input with respect to Analog Outputs and Remote Setpoint Input:
All other inputs and outputs with respect to relay contacts: 2000 VAC
Not isolated between Analog Output and Remote Setpoint commons.
SAFETY
UL Recognized Component, File #E156876, UL873, CSA 22.2 No. 24
Type 4X Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. No loss of performance during EMI disturbance at 10 V/m.
2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms:
Refer to the EMC Installation Guidelines section of the manual for additional
Panel latch can be installed for vertical or horizontal instrument stacking.
One piece tinted plastic bezel. Bezel assembly with circuit boards can be
removed from the case to change the output board without removing the case
from the panel or disconnecting wiring. Unit meets NEMA 4X/IP65
requirements for indoor use, when properly installed. Installation Category
II, Pollution Degree 2.
The P48 controls a process by receiving a linear DC signal representing the
Immunity to EN 50082-2
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
RF conducted interference
Power frequency magnetic fields
Simulation of cordless telephones
Emissions to EN 50081-2
RF interference
1 minute).
50 V working (2300 V for 1 minute).
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
Unit is panel mounted in a metal enclosure (Buckeye SM7013-0 or
Power Line and I/O cables routed in metal conduit connected to earth
For operation without loss of performance:
I/O cables routed in metal conduit connected to earth ground.
information.
for measurement, control, and laboratory use, Part 1.
equivalent) that provides at least 20 dB shielding effectiveness. Metal
panel is connected to earth ground.
ground.
Analog output may deviate during EMI disturbance.
Install power line filter, RLC#LFIL0000 or equivalent.
Install 2 ferrite cores, RLC#FCOR0000 or equivalent, to AC lines at
unit for frequencies above 5 MHz.
OR
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 61000-4-8
ENV 50204
EN 55011
Level 2; 4 Kv contact
Level 3; 8 Kv air
Level 3; 10 V/m
80 MHz - 1 GHz
Level 4; 2 Kv I/O
Level 3; 2 Kv power
Level 3; 10 V/rms
150 KHz - 80 MHz
Level 4; 30 A/m
Level 3; 10 V/m
900 MHz ± 5 MHz
200 Hz, 50% duty cycle
Enclosure class A
Power mains class A
1
2
3
FRONT PANEL FEATURES
display. One of the following parameters can be viewed in the lower display:
enabled, the control setpoint or power output (manual mode only) can be
directly modified in this mode.
and modified by use of the UP and DOWN buttons. Parameters are then entered
by the P button, which advances the user to the next parameter. Pressing the D
button immediately returns the controller to the normal operating mode without
changing the currently selected parameter.
HARDWARE FEATURES
process disturbance, thus providing excellent process control. Measurement
accuracy of 0.1% or better, provides close process control conforming to the
desired control setpoint value.
process control. The recommended two year re-calibration interval is easily
accomplished via the programming menu.
REMOTE SETPOINT INPUT
controller’s setpoint. The remote signal can be scaled independent to that of the
controller’s range. The controller’s response to local/remote setpoint transfers
can be programmed. Also, the remote signal is filtered by use of an adaptive
filter. With this filter, relatively large filtering time constants can be used
without suffering from long settling times. The time constant and filter disable
band are programmable. Additionally, the remote signal can also be velocity
limited (or ramped) to slow the controller’s response to changes in setpoint. This
results in a steady control response with no overshoot.
LINEAR DC ANALOG OUTPUTS
update time and filter (damping) time. These parameters permit flexibility in
process configuration. The output can be set for 0 to 10 V, 0 to 20 mA or 4 to
20 mA ranges and can be configured for control or for re-transmission of input
or setpoint values.
process input signal. The output can be scaled and converted independent of the
input signal and Main Linear DC output. This output is isolated from the input.
SETPOINT FEATURES
programming the setpoint range limit values. Additionally, safeguards from
inadvertent data entry can be programmed.
panel.
or any time a setpoint change is made, at a user programmable rate. This feature
reduces shock to the process and helps to minimize overshoot.
INPUT FEATURES
with varying or oscillating process characteristics, helping to provide better
control.
such as auto/manual transfer of the controller, reset alarm output(s), etc.
OUTPUT FEATURES
excessive power can cause damage. Programmable output cycle time, output
hysteresis, and dampening can reduce output activity without degrading control
accuracy. The main outputs can operate in PID, ON/OFF, or manual control
modes.
CONTROL AND ALARM OUTPUTS
available. Relay outputs can switch user applied AC or DC voltages for control
or alarm purposes.
In the normal operating mode, the unit displays the process value in the upper
The user scrolls through these parameters by pressing the D button. If
In the normal operating mode, parameters are selected by use of the P button
A fast 100 msec input sampling rate provides quick controller response to a
Low-drift, highly stable circuitry ensures years of reliable and accurate
The remote setpoint input facilitates the use of a remote signal to drive the
The Main Linear DC output has independent scaling, programmable output
A Second Linear DC output is dedicated for the re-transmission of the
The controller setpoint can be protected from out of range values by
A second setpoint can be selected by the user input and/or through the front
The setpoint ramp feature can be used to control the setpoint value at start-up
A programmable input filter can be used to stabilize readings from a process
The programmable user input can be used to control a variety of functions,
Programmable output power limits provide protection for processes where
In addition to the Linear DC output, there are up to three relay outputs
- Setpoint
- % Power Output
- Process Deviation
- Blank Display