T1611110 Red Lion Controls, T1611110 Datasheet - Page 2

no-image

T1611110

Manufacturer Part Number
T1611110
Description
DC, W/Relay Out, 2 Alarms, And User Input
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheet

Specifications of T1611110

Brand/series
T16 Series
Contact Form
SPST
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Mounting Type
Panel
Output Type
Relay
Power, Rating
4 W
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Termination
Screw
Voltage, Supply
24/18 to 36 VAC/VDC
Lead Free Status / Rohs Status
RoHS Compliant part
GENERAL SPECIFICATIONS
1. DISPLAY: 2 Line by 4-digit, LCD negative image transmissive with
2. ANNUNCIATORS:
3. POWER:
4. CONTROLS: Three rubber push buttons for modification and setup of
5. MEMORY: Nonvolatile E
6. ISOLATION LEVEL:
7. CERTIFICATIONS AND COMPLIANCES:
INPUT SPECIFICATIONS
1.
2. RTD INPUTS: (T16 only)
backlighting.
Top (Process) Display: 0.3" (7.6 mm) high digits with red backlighting.
Bottom (Parameter) Display: 0.2" (5.1 mm) high digits with green
Status Annunciators:
Display Messages:
Line Voltage Models:
Low Voltage Models:
controller parameters. One additional button (F1) for user programmable
function. One external user input (models with alarms) for parameter lockout
or other user programmable functions.
AC power with respect to all other I/O: 250 V working (2300 V for 1 min.)
Sensor input to analog output: 50 V working (500 V for 1 minute)
Relay contacts to all other I/O: 300 V working (2300 V for 1 minute)
DC power with respect to sensor input and analog output: 50 V working
SAFETY
UL Recognized Component, File #E156876, UL873, CSA 22.2 No. 24
SENSOR INPUT:
Sample Period: 100 msec (10 Hz rate)
Step Response Time: 300 msec typical, 400 msec max to within 99% of final
Failed Sensor Response:
Normal Mode Rejection: >40 dB @ 50/60 Hz
Common Mode Rejection: >120 dB, DC to 60 Hz
Overvoltage Protection: 120 VAC @ 15 sec max
Type: 2 or 3 wire
Excitation: 150 µA typical
Lead Resistance: 15 Ω max per input lead
Resolution: 1° or 0.1° for all types
backlighting.
O1 - Main control output is active.
O2 - Cooling output is active (when Alarm 2 is used for cooling).
A1 - Alarm 1 output is active.
A2 - Alarm 2 output is active.
°F, °C - Temperature units.
%PW - Output power percentage is shown in Bottom display.
MAN - Controller is in Manual Mode.
R - Ramping Setpoint indicator.
% - Percent indicator (P16 models only).
OLOL
ULUL
OPEN
SHrt
SENS
dddd
-ddd
85 to 250 VAC, 50/60 Hz, 8 VA
DC Power: 18 to 36 VDC, 4 W
AC Power: 24 VAC, ±10%, 50/60 Hz, 7 VA
(500 V for 1 minute)
Recognized to US and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
value with step input.
Main Control Output(s): Programmable preset output
Display: “OPEN”
Alarms: Upscale drive
Analog Output: Upscale drive when assigned to retransmitted input.
Ohms Linear Resistance
TYPE
385
392
672
- Measurement exceeds + sensor range
- Measurement exceeds - sensor range
- Open sensor is detected (T16 only)
- Shorted sensor is detected (RTD only)
- Measurement exceeds controller limits (P16 only)
- Display value exceeds + display range
- Display value exceeds - display range
Alpha = .003919
100 Ω platinum,
100 Ω platinum,
Alpha = .00385
Alpha = .00672
120 Ω nickel,
INPUT TYPE
2
PROM retains all programmable parameters.
-328 to +1112°F
-328 to +1112°F
-200 to +600°C
-200 to +600°C
-112 to +419°F
0.0 to 320.0 Ω
-80 to +215°C
RANGE
STANDARD
No official
No official
standard
standard
IEC 751
N/A
2
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms:
8. ENVIRONMENTAL CONDITIONS:
9. CONNECTION: Wire-clamping screw terminals
10. CONSTRUCTION: Black plastic alloy case and collar style panel latch.
11. WEIGHT: 6.3 oz (179 g)
3. THERMOCOUPLE INPUTS: (T16 only)
Type 4X Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY
For operation without loss of performance:
For operation without loss of performance:
Refer to the EMC Installation Guidelines section of this bulletin for
Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -40 to 80°C
Operating and Storage Humidity: 85% max relative humidity (non-
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
Shock According to IEC 68-2-27: Operational 20 g’s (10 g relay), 11 msec
Altitude: Up to 2000 meters
Panel latch can be installed for vertical or horizontal instrument stacking.
Black plastic textured bezel with transparent display window. Controller
meets NEMA 4X/IP65 requirements for indoor use when properly installed.
Installation Category II, Pollution Degree 2.
Types: T, E, J, K, R, S, B, N, C, and Linear mV
Input Impedance: 20 MΩ for all types
Lead Resistance Effect: 0.25 µV/Ω
Cold Junction Compensation: Less than ±1°C typical (1.5°C max) error
Resolution: 1° for types R, S, B and 1° or 0.1° for all other types
Immunity to EN 50082-2
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
RF conducted interference
Emissions to EN 50081-2
RF interference
W5/W6
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
Measurement input signal may deviate during EMI disturbance.
Install one ferrite core one turn, RLC #FCOR0000 or equivalent, to I/O
Process and analog output signal may deviate during EMI disturbance.
Install one ferrite core one turn, RLC #FCOR0000 or equivalent, to I/O
additional information.
condensing) from 0°C to 50°C
direction for 1.5 hours, 2 g’s.
in 3 directions.
over ambient temperature range.
TYPE
mV
T
E
K
R
S
B
N
C
J
for measurement, control, and laboratory use, Part I
cables at unit.
cables and power cable at unit.
+149 to +1820°C
+300 to +3308°F
-328 to +1382°F
-328 to +1400°F
-200 to +1250°C
-328 to +2282°F
-200 to +1300°C
-328 to +2372°F
DISPLAY RANGE
+32 to +3214°F
+32 to +3214°F
+32 to +4199°F
-200 to +400°C
-328 to +752°F
-200 to +750°C
-200 to +760°C
0 to +1768°C
0 to +1768°C
0 to +2315°C
-5.00 mV to
56.00 mV
(+) Orange
(+) Yellow
(+) Violet
(+) White
standard
standard
standard
standard
(+) Blue
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
EN 55011
(-) Red
(-) Red
(-) Red
(-) Red
(-) Red
ANSI
N/A
No
No
No
No
WIRE COLOR
(+) Orange
(+) Brown
(+) Yellow
(+) Brown
(+) White
(+) White
(+) White
standard
standard
BS 1843
(-) Blue
(-) Blue
(-) Blue
(-) Blue
(-) Blue
(-) Blue
(-) Blue
N/A
No
No
Level 2; 4 kV contact
Level 3; 8 kV air
Level 3; 10 V/m
80 MHz - 1 GHz
Level 4; 2 kV I/O
Level 3; 2 kV power
Level 3; 10 V/rms
150 KHz - 80 MHz
Enclosure class A
Power mains class A
STANDARD
E988-96
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ITS-90
ASTM
N/A
1
2