Specifications
Model Rating
Nominal Operating Frequency
Factory Default Vac
Operating Voltage
Range Without Battery Operation
Maximum Allowable Vac
Input Frequency Without
Battery Operation
Factory Default Vac
Frequency
Waveform
Main Mode Overload
Type
Quantity x V
Back-up Time
Recharge Time (Internal Batteries)
Disable Bypass Operation
Re-enable Bypass Operation
Disable Bypass operation
Amps Rating
Input Power Connection
Output Power Connection
Input Branch Circuit Breaker
Unit (H x W x D)
Shipping (H x W x D)
Shipping Weight - lbs (kg)
User Configurable Vac
Includes:
Catalog Number
contact Technical Services at (800) 377-4384 with any questions.
>200% for 96 milliseconds; 131 - 199% for 2 seconds; 112- 129% for 10 seconds with transfer to bypass
Visit our website at www.solaheviduty.com or
Two IEC320 C19 16A/250V sockets, Manual Bypass Switch with Indicator Lamps
Uninterruptible Power Systems
Dimensions inches (mm)
Bypass Protection Limits
Power Distribution Box
Output AC Parameters
220/230/240 Vac (May be modified using configuration program)
Input AC Parameters
If input voltage returns to within ±10% of nominal output voltage
Battery Parameters
When the input frequency prevents synchronous operation
3 hrs. to 90% capacity after full discharge into 100% load
If input voltage exceeds ±15% of the nominal voltage
3-Wire Hardwired, 6-10 mm
3-Wire Hardwired, 6-10 mm
Valve-regulated, non-spillable, lead acid
19.7 x 22.05 x 27.17 (500 x 560 x 690)
16.9 x 8.7 x 21.5 (430 x 221 x 547)
50 or 60 Hz (Factory Default = 50)
See Back-up Times Chart
50 Hz or 60 Hz, Nominal
32A, supplied by user
6 kVA / 4,200W
176 – 276 Vac
S4K5U6000-5
175.3 (79.5)
40 - 70 Hz
Sinewave
32 Amps
20 x 12V
230 Vac
276 Vac
230 Vac
2
2
(8-10 AWG)
(8-10 AWG)
79