DIN2R-40-120-L1 SUPERIOR ELECTRIC, DIN2R-40-120-L1 Datasheet

no-image

DIN2R-40-120-L1

Manufacturer Part Number
DIN2R-40-120-L1
Description
DIN Rail Mounted Surge Suppressor
Manufacturer
SUPERIOR ELECTRIC
Series
DIN2R-40r
Type
Single-Poler
Datasheet

Specifications of DIN2R-40-120-L1

Suppressor Type
Data Line
Voltage Rating
120VAC
Operating Voltage Range
120VAC To 240VAC
Peak Surge Current
40kA
Connector Type
Screw Terminal
Frequency Max
64Hz
Brand/series
STABILINE®/DIN2R-40 Series
Current, Surge
40 kA
Dimensions
18 W × 90 H × 67 D mm
Ip Rating
IP20
Mounting Type
DIN Rail
Primary Type
Transient Voltage Surge Suppressor
Termination
Screw
Voltage, Operating
150 V
Voltage, Supply
120, 120/240, 120/208 V
Wire Size
10-4 AWG
For Use With
Industrial Equipment
UL Recognized for USA and Canada
DIN2R-40 Series Benefits
u
u
u
u
u
u
DIN Rail mountable surge
protection devices
Replaceable SPD modules
- eliminate costly, time-consuming
- simple snap “in/out” design for
- compact, lightweight yet rugged
Visual monitor advises protection
present status
Model choices allow for single mode or
all-mode protection strategies
Each protector module / fixed base are
“keyed” to ensure proper application
All protectors (except N-G model)
equipped with signaling relay
contacts for remote monitoring of
protection status
Automatic Voltage Regulators • Power Conditioners • Uninterruptible Power Supplies
replacement wiring
rapid maintenance
Replaceable Plug-In Surge Protection Module
DIN2R-40 Series STABILINE Transient Voltage Surge Suppressors
are single pole, parallel-connected, MOV technology Class II,
Category B Surge Protective Devices suitable for use in AC elec-
trical power systems for protection against surge and transient
activity. Each protector provides 40 kA Surge Amp Capacity
protection in maintenance free, low profile, IP20 enclosure, DIN
Rail mountable module.
Installation
DIN2R-40 Protectors are installed/connected in parallel with
the line and the equipment to be protected. The DIN2R-40 unit
should be installed down stream of a 125 A maximum fuse or
breaker. If pre-existing fuses or breakers are present, then the
fusing or breaker used for the DIN2R-40 protector should have
a lower rating in order to be properly coordinated, as per ap-
plicable electrical regulatory standards. The short circuit current
rating for these DIN2R-40 protectors are 25,000 Amps using a
50A Class J time delayed fuse.
Remote Monitoring
All DIN2R-40 protectors (except N - G protector) come standard
with one remote monitoring relay with “dry Form C contacts”
per module. The contact can be used to drive several different
types of indicators such as a remote light indicator or an audible
alarm. The contact ratings are 250V RMS max, 2A max. The
connection to the remote signal is through the screw terminals.
Visual Protection Status
All DIN2R-40 protectors are maintenance free devices. If the unit
is subjected to a prolonged over-voltage condition, an internal
thermal element will activate, disconnecting the DIN2R-40 from
the line. When the unit is no longer providing protection the win-
dow on the front of the DIN2R-40 becomes red and a replace-
ment module will be required.
DIN2R-40 Series — Surge Protective Devices (SPD)
Parallel-Connected Design/Single Pole (Mode) Protectors

Related parts for DIN2R-40-120-L1

DIN2R-40-120-L1 Summary of contents

Page 1

... All DIN2R-40 protectors are maintenance free devices. If the unit is subjected to a prolonged over-voltage condition, an internal thermal element will activate, disconnecting the DIN2R-40 from the line. When the unit is no longer providing protection the win- dow on the front of the DIN2R-40 becomes red and a replace- ment module will be required. ...

Page 2

... Model Typical Service Configurations Numbers 1 ∅, 120 VAC, 2-Wire, w/ground DIN2R-40-120-L1 1 ∅, 120/240 VAC, 3-Wire SPLIT-PHASE, w/ground 3 ∅, 208Y/120 VAC, 4-Wire WYE, w/ground 1 ∅, 220 VAC, 2-Wire, w/ground DIN2R-40-220-L1 3 ∅, 380Y/220 VAC, 4-Wire WYE, w/ground 3 ∅, 220 VAC, 3-Wire DELTA 1 ∅ ...

Page 3

... Ibs (0.11 kg) L-N; L-G; L-L protectors use MOV technology and N-G protector uses Gas Tube 47-64 Hz DIN2R-40 protectors incorporate an internal thermal disconnect system with time-delayed Class J,30A-125A over current fuses Applications Control panels feeding PLCs, VSDs and other control system components ...

Page 4

... Ground Protector Telephone and Fax Numbers Telephone: 860-507-2025 Fax: 860-507-2050 Customer Service 860-507-2025, Ext 70782 Product Application 860-507-2025, Ext 72058 Printed in USA F7050 REV B 7/09 ©2009 Superior Electric 2.63 in (67 mm) .71 in (18 mm (51 mm L/N TVSS UL 1449 ed2 S A SABS IEC 61643-1 ...