Specifications of ESP240M1

Suppressor Type
Mains
Voltage Rating
240Vrms
Operating Voltage Range
200Vrms To 280Vrms
Peak Surge Current
60kA
Connector Type
Screw Terminal
Control Voltage Ac Max
280V
Current Id
RoHS Compliant
Electrical specification
Transient specification
Mechanical specification
www.furse.com
Mains supplies & power distribution systems
Nominal voltage (RMS)
Working voltage (RMS)
Frequency range
Current rating (supply)
Leakage current (to earth)
Indicator circuit current
Volt free contact
Temperature range
Connection type
Conductor size (stranded)
Earth connection
Volt free contact
Weight
Dimensions
* Minimum permissible load is 5V DC, 10mA to ensure reliable contact operation.
Let-through voltage (all conductors)
6kV 1.2/50µs open circuit voltage,
3kA 8/20µs short circuit current to:
BS 6651:1999 Appendix C, Cats C-Low & B-High
IEEE C62.41-1991
SS CP 33:1996 Appendix F
AS 1768-1991 Appendix B, Cat B
UL1449 mains wire-in
4kV 1.2/50µs open circuit voltage,
2kA 8/20µs short circuit current to:
IEC 1000-4-5:1995
2kV 1.2/50µs open circuit voltage,
1kA 8/20µs short circuit current
5kA 8/20µs to NFC 61-740
2.5kA 8/20µs to BS EN 60099-1:1994
6kV 0.5µs 100kHz ring wave, 500A to:
IEEE C62.41-1991
AS 1768-1991 Appendix B, Cat B
Maximum surge current
1 The maximum transient voltage let-through the protector throughout the test (±5%), phase to neutral, phase to earth and neutral to earth.
2 Formerly IEEE 587 and ANSI C62.41.
3 Tested with 8/20µs waveshape to BS 6651:1999 Appendix C. Note:The electrical system, external to the unit, may constrain the actual current
- current rating
- nominal voltage (RMS)
- between any two conductors
- total unit to earth
rating achieved in a particular installation.
- unit
- packaged
*
2
2
Location Cats C1 & B3
Location Cat B3
3
ESP 120 M1
120V
90-150V
40-60Hz
Direct connection to supplies up to 100A
Connection via series fuses to supplies greater than 100A
See installation instructions
<250µA
<10mA
Screw terminal
1A
250V
ESP 120 M1
-40 to +70ºC
Screw terminal
16mm
Screw terminal
Connect via screw terminal with conductor up to 2.5mm
0.6kg
0.7kg
1
2
ESP 120 M1 ESP 208 M1 ESP 240 M1 ESP 415 M1
400V
385V
370V
445V
395V
Available
on request
30kA
60kA
Mains supplies & power distribution systems | Protectors
ESP 208 M1
208V
156-260V
40-60Hz
<250µA
<10mA
Screw terminal
1A
250V
ESP 208 M1
-40 to +70ºC
Screw terminal
16mm
Screw terminal
1.0kg
1.1kg
2
400V
385V
370V
445V
395V
Available
on request
30kA
120kA
ESP 120 M1, ESP 208 M1
ESP 240 M1, ESP 415 M1
ESP 240 M1
240V
200-280V
40-60Hz
<250µA
<10mA
Screw terminal
1A
250V
ESP 240 M1
-40 to +70ºC
Screw terminal
16mm
Screw terminal
0.6kg
0.7kg
30kA
60kA
600V
570V
530V
690V
590V
510V
2
ESP 415 M1
415V
346-484V
40-60Hz
<250µA
<10mA
Screw terminal
1A
250V
ESP 415 M1
-40 to +70ºC
Screw terminal
16mm
Screw terminal
1.0kg
1.1kg
600V
570V
530V
690V
590V
510V
30kA
120kA
2