NLP250N-99S12J Emerson Network Power, NLP250N-99S12J Datasheet

POWER SUPPLY, AC/DC, 12V

NLP250N-99S12J

Manufacturer Part Number
NLP250N-99S12J
Description
POWER SUPPLY, AC/DC, 12V
Manufacturer
Emerson Network Power
Type
Open Framer
Datasheet

Specifications of NLP250N-99S12J

Power Supply Type
Open Frame
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
12V
Output Current
21A
Power Rating
250W
Input Voltage
85V AC To 264V AC
Length
177.8mm
Width
101.6mm
Product
Switching
Commercial/medical
Medical
Output Power Rating
250 W
Number Of Outputs
1
Output Voltage (channel 1)
12 V
Output Current (channel 1)
21 A
Mounting Style
Panel
Dimensions
7 in L x 4 in W x 1.5 in H
Open Frame/enclosed
Open Frame
Output Current (max)
21A
Output Power (max)
250W
Input Frequency
47 to 63Hz
Efficiency
86%
Screening Level
Commercial
Product Length (mm)
177.8mm
Product Height (mm)
38.1mm
Product Depth (mm)
101.6mm
Operating Temperature Min Deg. C
0C
Operating Temperature Max Deg. C
70C
Pin Count
18
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
NLP250N-99S12J
Manufacturer:
ARTESYN
Quantity:
1 000
Special Features
• Medical safeties
• Active PFC and
• 250 W on main channel with
• Low profile fits 1U applications
• U-Channel for maximum
• Optional cover (CJ suffix)
• 5 V standby output
• 12 V fan output
• Integrated control and
• Overcurrent, overvoltage and
• Compliance to EN55022-B
• Dual AC fuses
• RoHS compliant
• 2 year warranty
Safety
NLP250 Medical
Series
Single Output
Total Power:
Input Voltage: 85 - 264 VAC
# of Outputs:
EN61000-3-2 compliant
forced air
thermal performance
monitoring features
overtemperature protection
conducted noise standard
VDE0750/EN60950
IEC950/IEC60601-1
File No. 1177400-3336-0759
UL60601-1
File No. E186249
Certificate No. 40014041
CB Ref DE1-36628
250 W
Single
Electrical Specifications
Input
Input voltage range:
Input frequency range:
Input surge current:
Safety ground leakage current:
Input current:
Input fuse:
Output
Adjustment range:
Total regulation:
(line and load)
Turn-on delay:
Temperature coefficient:
Overvoltage protection:
Short circuit protection:
Minimum output current:
Maximum power:
Transient response:
Auxiliary outputs:
(See Note 8, page 3)
All specifications are typical at nominal input, full load at 25
Universal input
264 Vac (cold start)
264 Vac, 50 Hz
120 Vac @ 250 W
230 Vac @ 250 W
UL/IEC127
200 LFM forced air
250 LFM with cover
Main output
Main output
Auxiliary outputs
@ 120 Vac Input
Main output
50 - 100%
Step at 0.5 A/µs
Main output
Cyclic operation
Singles
5 Vsb
12 V (fan)
°
C unless otherwise stated
Embedded Power for
Business-Critical Continuity
85 - 264 Vac
47 - 63 Hz
40 A max.
150 µA
2.78 A rms
1.36 A rms
T6.4 AH, 250 Vac In live and
neutral
250 watts
± 5%
± 2.0%
± 5.0%
2.0 s max.
5.0% or 250 mV
max. dev., 1 ms max
recovery to 1%
±0.02%/°C
115%, ± 5%
Continuous
0 A
5 V @ 1.0 A
12 V @ 0.3A
NLP250 Medical Series
Rev.10.1.09_181
1 of 4

Related parts for NLP250N-99S12J

NLP250N-99S12J Summary of contents

Page 1

NLP250 Medical Series Single Output Total Power: 250 W Input Voltage 264 VAC # of Outputs: Single Special Features • Medical safeties • Active PFC and EN61000-3-2 compliant • 250 W on main channel with forced air • Low profile fits 1U applications • U-Channel for maximum thermal performance • Optional cover (CJ suffix) • standby output • fan output • Integrated control and ...

Page 2

EMC Characteristics (5) Conducted emissions: Harmonic current correction: Voltage flicker: ESD air: ESD contact: Radiated immunity: Fast transients: Surge: Conducted immunity: Voltage dips: General Specifications Hold-up time: Efficiency: Isolation voltage: Safety approvals (see Note 6, page 3): Weight: MTBF (@25º C): Environmental Specifications Thermal performance: Relative humidity: Altitude: Vibration (See Note 7, page 3): Shock: EN55022, FCC part 15 Level B EN61000-3-2 Compliant EN61000-3-3 Compliant EN61000-4-2 Level 3 EN61000-4-2 Level 3 EN61000-4-3 Level 3 EN61000-4-4 Level 3 EN61000-4-5 ...

Page 3

... J3 JP1 1 VR7 0.25 (6.35) Embedded Power for Business-Critical Continuity Model Numbers (9, 10) ± 2.0% NLP250N-99S12J ± 2.0% NLP250N-99S24J CUSTOMER MOUNTING HOLES MAX. SCREW PENETRATION 0.08IN 6-32 M3.0 5.850 (148.59) 6.250 (158.75) M3.0 4 PLACES 6-32 4 PLACES 4.700 (119.38) 5.500 (139.70) BOTTOM VIEW Rev ...

Page 4

... For global contact, visit www.PowerConversion.com techsupport.embeddedpower @emerson.com While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Emerson Network Power. The global leader in enabling business-critical continuity. AC Power Connectivity DC Power Embedded Computing Embedded Power Monitoring Outside Plant Power Switching & Controls Precision Cooling Racks & ...

Related keywords