IEG6-1-72-15.0-01-V AIRPAX, IEG6-1-72-15.0-01-V Datasheet - Page 22

CIRCUIT BREAKER, HYD-MAG, 1P, 240V, 15A

IEG6-1-72-15.0-01-V

Manufacturer Part Number
IEG6-1-72-15.0-01-V
Description
CIRCUIT BREAKER, HYD-MAG, 1P, 240V, 15A
Manufacturer
AIRPAX
Series
IEGr
Datasheet

Specifications of IEG6-1-72-15.0-01-V

Input Voltage Vac
240V
No. Of Poles
1
Current Rating
15A
Interrupting Capacity
7.5kA
Dielectric Strength
3.75kV
Trip Time
20s
Voltage Rating Vdc
80V
Actuator Style
Toggle
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
125
LEG DECISION TABLES
The ordering code for LEG circuit breakers may be
determined by following the decision steps in the tables
shown here.
The coding given permits a self-assigning part number
but with certain limitations. Special applications may
require a factory-assigned part number. Typical examples
are units with mixed ratings, combinations of styles, or
constructions not listed in the third decision table. With
these, it is suggested that order entry be by description
and/or drawings and a part number will be established.
Additionally, it is standard policy to establish a factory-
assigned part number whenever a descriptive drawing
exists to provide cross reference, traceability and
manufacturing control.
When specifying a circuit breaker for AC motor start
or high inrush applications, the peak amplitude and surge
duration should be specified for factory assistance in
rating selection.
For example, the following is the code for a single
pole, LEG screw type terminal, series unit with auxiliary
switch, designed for operation in a 50/60Hz circuit. It has
a short time delay, a rating of 20 amperes, a black marked
handle and is VDE approved.
To determine the ordering number for your particular LEG
unit, simply follow the steps shown. You may use this
number to place an order or as a reference for further
questions you may have.
Notes:
A. When “A” (metric thread mounting) is specified in the sixth decision in
B. LEG, LEGH, LEGS, LEGHS, LEGZX and LEGBX circuit breakers are
combination with screw terminal option in the second decision, metric
screw terminals are supplied.
designed to meet 8mm creepage and clearance requirements for instal-
lation Category III, Pollution Degree 3, Case A as measured in IEC 664.
Intended for use in equipment designed to comply with IEC 601 and 950
and VDE 0804 and 0805.
LEG Series - Decision Tables
LEG
LMG
LEGH
LMGH
Note: All types are UL489 listed, CUL certified
* Only one auxiliary switch is normally supplied on two pole
-1
-1REC4
-1REC5
-1REG4
-1RS4
-1RLS4
-3
1
Type
3
units. Switch is located in the right-hand pole (viewed from
terminal end) unless otherwise specified.
First Decision
Select Type and Terminal
Internal Configuration
Third Decision
Description
Series
Series w/ auxiliary switch *
.110 quick connect
Series w/ auxiliary switch *
.187 quick connect
Series w/ auxiliary switch*
(gold contacts)
.110 quick connect
Series w/ alarm switch*,
electrical trip,
.110 Q.C. terminals
Series w/ alarm switch*,
electrical trip, mid-trip only,
.110 Q.C. terminals
Shunt
One toggle handle per unit
One toggle handle per unit
mid-trip indication
One toggle handle per pole
One toggle handle per pole
mid-trip indication
Push-on
Terminals
1
11
*Not available in toggle seal handle type.
2
Second Decision
Poles and Terminals
Screw
Terminals
6
66
Note: Add "F" for flat screw terminals
* Not available on mid-trip units
S
ZX
BX
Handle and Mounting Options
Standard toggle/mounting,
no designation required
Toggle w/ snap-in mounting
ZX Rocker w/ integral mounting*
BX Rocker w/ integral mounting
Example:
LEG
Single pole
Two pole
http://airpax.sensata.com/
-61
-62
-63
-69
1
For addition of inertial delay, add an “F” to any
delay numeral.
* CEG types are only available with DC ratings
The shaded areas denote VDE and CCC
(if applicable) Approval options. This approval
requires the addition of a V at the end of the
part number. The V will be added to any part
number formed entirely from shaded decisions.
If non-shaded areas are selected, the unit will
not be VDE or CCC Approved, but other
approvals still apply.
This approval requires the addition of a C at the end
of the part number. The unit will not be VDE Approved.
4
V = VDE and CCC Approved
C = CCC Approved
Fourth Decision
Frequency and Delay
50/60Hz short delay
50/60Hz long delay
50/60Hz motor start
50/60Hz 125% instant trip
6 - 1REC4 - 61 - 20.0 - 01 - V
2
3
4
5
7

Related parts for IEG6-1-72-15.0-01-V