LPS-RK-200SP Cooper/Bussmann, LPS-RK-200SP Datasheet

FUSE, 200A, 600V, TIME DELAY

LPS-RK-200SP

Manufacturer Part Number
LPS-RK-200SP
Description
FUSE, 200A, 600V, TIME DELAY
Manufacturer
Cooper/Bussmann
Series
LPS-RKr
Datasheet

Specifications of LPS-RK-200SP

Voltage Rating Vdc
300V
Voltage Rating Vac
600V
Fuse Current
200A
Blow Characteristic
Time Delay
Fuse Size Imperial
1.61 X 9.63"
Peak Reflow Compatible (260 C)
No
Current Rating
200A
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Catalog Symbol: LPS-RK_SP (600V)
Ampere Rating: 70 to 600A
Voltage Rating:
ac: 600V (or less)
dc: 300V (or less)
Interrupting Rating:
ac: 300,000A RMS Sym.
dc: 100,000A
Agency Information:
UL Listed–Special Purpose**, Guide JFHR, File E56412
CSA Certified, (200,000 AIR) Class 1422-02, File 53787,
Catalog Numbers
LPS-RK-70SP
LPS-RK-80SP
LPS-RK-90SP
LPS-RK-100SP
LPS-RK-110SP
LPS-RK-125SP
Available with tin plate option. Add suffix “-TP”. (Ex.: LPS-RK-100SP-TP)
Carton Quantity and Weight—LPS-RK (600Vac)
Ampere
Ratings
70–100
110–200
225–400
450–600
** Meets all performance requirements of UL Standard 248-12 for Class RK1
LOW-PEAK
Dual-Element, Time-Delay Fuses
Class RK1 –– 600 Vac/300 Vdc
*Weight per carton.
10-2-02
Class RK1 per CSA C22.2 No. 248.12
fuses.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
Qty.
1
1
1
1
SB02295
Carton
Lbs.
2.20
1.10
2.36
3.44
LPS-RK-150SP
LPS-RK-175SP
LPS-RK-200SP
LPS-RK-225SP
LPS-RK-250SP
LPS-RK-300SP
®
Kg.
1.0
0.5
1.1
1.5
Weight*
LPS-RK-350SP
LPS-RK-400SP
LPS-RK-450SP
LPS-RK-500SP
LPS-RK-600SP
Dimensional Data
Dimensions
Ampere Ratings
Features:
• High degree of current-limitation for maximum short-circuit
• Type 2 protection for IEC and NEMA starters when
• High inrush current motor protection.
• Time-delay permits 130% FLA sizing for back-up motor over-
• Low watt loss power consumption.
• Electrically isolated end caps.
• 300Vdc, UL Listed.
Applications:
• Branch distribution
• Motors
• Transformers
• Solenoids
• General purpose circuits
Fuse Reducers For Class R Fuses
Equipment
Fuse Clips
200A
400A
600A
*Single reducer only (pair not required).
For additional information, see Data Sheet: 1118.
properly sized.
load protection, and single-phasing protection.
protection.
110-200
225-400
450-600
70-100
(inches)
Fuse (Case)
11.63 (± 0.094)
13.38 (± 0.094)
Desired
7.88 (± 0.062)
9.63 (± 0.062)
100A
100A
200A
100A
200A
400A
Size
A
Recommended fuseblocks for
Class R 600V fuses
See Data Sheet: 1111
“A”
Bussmann
Catalog Number
Form No. LPS-RK 70-600
1.11 (± 0.020)
1.61 (± 0.020)
2.36 (± 0.020)
2.88 (± 0.020)
LPS-RK
No. 2621-R
No. 2641-R
No. 642-R
No. 2661-R
No. 2662-R
No. 2664-R*
(Pairs)
70-600A
600V
“B”
Data Sheet: 1002
Page 1 of 3
B
®

Related parts for LPS-RK-200SP

LPS-RK-200SP Summary of contents

Page 1

... CSA Certified, (200,000 AIR) Class 1422-02, File 53787, Class RK1 per CSA C22.2 No. 248.12 Catalog Numbers LPS-RK-70SP LPS-RK-150SP LPS-RK-80SP LPS-RK-175SP LPS-RK-90SP LPS-RK-200SP LPS-RK-100SP LPS-RK-225SP LPS-RK-110SP LPS-RK-250SP LPS-RK-125SP LPS-RK-300SP Available with tin plate option. Add suffix “-TP”. (Ex.: LPS-RK-100SP-TP) Carton Quantity and Weight—LPS-RK (600Vac) ...

Page 2

... LOW-PEAK ® Dual-Element, Time-Delay Fuses Class RK1 –– 600 Vac/300 Vdc Time-Current Characteristic Average Melt 10-2-02 SB02295 Bussmann ® LPS-RK 70-600A Form No. LPS-RK 70-600 Page Data Sheet: 1002 ...

Page 3

... Bussmann LPS-RK 70-600A B 600A 400A 200A 100A Form No. LPS-RK 70-600 Page Data Sheet: 1002 ® ...