NZMN2-M125 MOELLER, NZMN2-M125 Datasheet - Page 8

MCCB, 125A, 50KA, 3P, MOTOR PROTECT

NZMN2-M125

Manufacturer Part Number
NZMN2-M125
Description
MCCB, 125A, 50KA, 3P, MOTOR PROTECT
Manufacturer
MOELLER
Series
NZMNr
Datasheet

Specifications of NZMN2-M125

No. Of Poles
3
Voltage Rating Vac
415VAC
Mounting Type
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Breaking Capacity Current Ac
50kA
Current Rating
125A
External Depth
68mm
External
RoHS Compliant
Notes
Notes
XSV = plug−in unit
XAV = withdrawable unit
TM = thermomagnetic
E = electronic
8
For rated operational voltage switching on 3 contacts the following applies: DC correction factor for
instantaneous release response value NZM1: 1.25, NZM2: 1.35
Setting for I
Details apply for 3−pole system protection circuit−breaker with thermomagnetic release
NZM(H)1(2)−A...
Switching of one pole via two series contacts
For NA switch switching capacity with NZM...1−...(C)NA the following applies: 480 Y/277 V from 60
A
For AC−3 rated operational current with NZM4 the following applies: 400 V: max. 650 kW; 690 V:
max. 600 kW
For NA switch switching capacity with NZML2 and NZML3 the following applies: Current Limiting
switch to UL489
For 3−pole system protection circuit−breaker the AC−3 specification is not applicable
For NA switch switching capacity with NZML4 at 240 V 60 Hz the following applies: on request
For current heat loss per pole the specification refers to the maximum nominal current of the frame
size.
For 3−pole system protection circuit−breaker the following
applies: 690 V
For 3−pole system protection circuit−breaker the following applies: 400/415 V 7500 switching
operations
Maximum back−up fuse, if the expected short−circuit currents at the installation location exceed the
switching capacity of the circuit−breaker.
Higher switching capacity on request
Flat conductor terminal – – –
1600 A
i
at DC = setting I
i
AC/DC correction factor
Switching of one pole via three series
contacts

Related parts for NZMN2-M125