S201MC63 ABB, S201MC63 Datasheet - Page 20

no-image

S201MC63

Manufacturer Part Number
S201MC63
Description
MCB, 1 POLE, 63A, 10KA, C CURVE
Manufacturer
ABB
Series
System Pro M Compactr
Datasheet

Specifications of S201MC63

No. Of Poles
1
Voltage Rating Vac
230V
Mounting Type
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
IEC/EN 60898, IEC/EN 60947-2, VDE 0641 Part 11, UL 1077, CSA
Current Rating
63A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
System
pro M compact
Description
Residual-current protective devices have a balance or, as the case may be, differential current transformer as measuring device that is
connected with permanent magnet trip via the secondary winding. Residual-current protective devices cover a.c. fault current and
pulsating d.c. fault current and are insensitive to current rushes up to 250 A, selective and short-time delayed tripping types up to 3,000 A).
Pulse shape 8/20 according to DIN VDE 0432 Part 2.
STOTZ residual-current protective devices are surge-proof and thus insensitive to transient leakage current to earth, as may occur e.g.
when switching fluorescent lamps, X-ray apparatus, IT systems and also thyristor control. (The value of the surge strength is indicated in
the technical data information regarding the switching variants).
Protection through RCD of types AC, A and B according to IEC 755
20
Selective RCCB F 200S
Is installed centrally and operates on a time-selective basis with respect to more sensitive downstream residual-current devices.
The result is a high degree of service security, as in the case of a fault, only the circuit affected will be switched off.
Due to their surge strength of up to 5,000 A/3,000 A, nuisance tripping of STOTZ main RCCBs caused by remote strike is ruled out.
They are therefore the perfect choice for the connection of freezers and agricultural applications (e.g. fans in intensive livestock husbandry)
according to DIN VDE 0100 Part 705.
Short-time delayed RCCBs F 200 R
are RCCBs with high surge strength needed where apparatus causes high leakage currents when switched on or off (e.g. lighting circuits
with ballast, long lines).
Application
To obtain a better level of security in all wiring systems, as well as in supply areas with respect to which codes of practice
recommend or require the use of residual-current protective devices.
Tasks
Protection against electric shock
Measures for the protection against electric shock as provided for in DIN VDE 0100 Part 410. These measures are:
form of residual current
sinusoidal a.c.
pulsating d.c.
smooth d.c.
Protection from indirect touch – as fault protection through disconnection of circuit in the case of excessive touch voltage caused by
short circuit to exposed conductive part.
Protection from direct touch – as additional protection through disconnection when conductive parts are touched. Dangerous leakage
current is switched off within the shortest possible time if the rated residual current of the circuit-breakers is I
people protector FS 201 I
Protection against fire – protection against fire ignited by electricity if the nominal residual current of the circuit-breaker is I
®
n
10 mA.
suddenly applied
suddenly applied with/without
superimosed smooth
d.c. of 6 mA
Residual-current-operated circuit breaker
F 200 series
slowly rising
slowly rising
a.c.- sensitive
F 200 AC
type AC
correct functioning of RCD
current-sensitive
pulsating
type A
F 200
n
30 mA, in the case of
d.c.-sensitive
n
type B
300 mA.