K2CU-F40A-C AC16-40AAC100 Omron, K2CU-F40A-C AC16-40AAC100 Datasheet - Page 4

no-image

K2CU-F40A-C AC16-40AAC100

Manufacturer Part Number
K2CU-F40A-C AC16-40AAC100
Description
HEATER FAULT DETECTOR
Manufacturer
Omron
Series
K2CUr
Datasheets

Specifications of K2CU-F40A-C AC16-40AAC100

Current Rating
16 ~ 40 A
Mounting Type
Panel
Operational Type
Large, Built in Transformer
Voltage - Supply
100 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Gate Input
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
K2CU-F40A-CAC16-40AAC100
K2CUF40ACAC1640AAC100
K2CU-F Series
When power is supplied to the heater (when the contactor is ON), a
current flows through the wires to the heater elements. At the same
time, a voltage is imposed on the power circuit of the K2CU-F.
The current flowing to the heater wires is detected by the detector
sections through each Current Transformer (CT) incorporated by the
K2CU-F.
The current signals transmitted by the two CTs are sent to the cur-
rent-voltage converters, smoothing circuits, and comparators as
shown in the diagram.
K2CU-P Series
The K2CU-P operates basically in the same way as the K2CU-F.
The comparator compares external current signals and the reference
value and outputs the result of the comparison to the output circuit.
Heater elements
Power supply
Power supply
Heater elements
CT
2
CT
1
Note: The dotted lines indicate the line conductors passing through the windows of the current transformers.
2
1
Contactor
Contactor
CT
http://www.ia.omron.com/
Note: The heater and the operating power supply
connected via terminals 6 and 8 or terminals
7 and 8 must be turned ON at the same time.
To each circuit
To each circuit
Alarm indicator
Output relay
200/220 V 100/110 V
X
Alarm indicator
Output relay
6
S
1
X/c
X
X/c
7
S
2
CM
b
a
5
4
3
8
1
1
The signal generated by the reference voltage generator is sent to
the setting circuit to provide a reference value. The reference value is
sent to the comparators. Each comparator compares its heater ele-
ment current input and the reference value. If the input is lower than
the reference value, a signal is sent to the output circuit.
There are two detector sections operating independently. If either of
the input signals from the CTs is lower than the reference value, the
output relay and alarm indicator will be activated.
The K2CU-F incorporates a voltage fluctuation compensation func-
tion which automatically corrects the reference value if the supply
voltage fluctuates.