Y92F-71 Omron, Y92F-71 Datasheet

no-image

Y92F-71

Manufacturer Part Number
Y92F-71
Description
ADAPTER H3CR 78MM BODY
Manufacturer
Omron
Datasheets

Specifications of Y92F-71

Accessory Type
Panel Mount Adapter, Frame
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
H3CR-G and H3CR-H Series
For Use With
Z2387 - RELAY TIMER 0-12SEC OFF-DELAYZ2386 - RELAY TIMER 0-12MIN OFF-DELAY
Color
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
Y92F71
Economical, Compact, High-performance,
DIN 48 × 48-mm Ground Fault Relay for Low
Voltages
• Performs continuous monitoring and detection of ground faults
• Higher reliability ensured with improved resistance to high-fre-
• Ground Fault Relays and through-type ZCTs (zero-phase cur-
• The through-type ZCTs are equipped with test terminals, allow-
Model Number Structure
■ Model Number Legend
1. Ground Fault Relay
2. Operating Time and Reset Method
Ordering Information
■ List of Models
Ground Fault Relays
ZCTs (Zero-phase Current Transformers)
K6EL-@@
Type
High-speed models
Delayed models
Rated current
50 A
100 A
200 A
400 A
600 A
1,000 A
in low-voltage circuits due to the deterioration of insulation in
electrical devices.
quency noise when used for inverter loads.
rent transformers) are mutually compatible.
ing operation tests for Ground Fault Relays to be performed with
ease.
Ground Fault Relay
K6EL
None: 0.1 s manual reset
A:
1
0.3/0.8 s (switchable) manual reset
2 3
Sensed current
Operating time
Less than 0.1 s
0.3/0.8 s (switchable)
Type
OTG-L21
OTG-L30
OTG-L42
OTG-L68
OTG-L82
OTG-L156
Model
Sensed current
Indoor through-type models
Type
K6EL-30
---
21 mm
30 mm
42 mm
68 mm
82 mm
156 mm
High-sensitivity
Diameter of through-hole
30 mA (fixed)
models
3. Sensed Current
30:
50:
100: 100 mA/200 mA (switchable)
200: 200 mA/500 mA (switchable)
500: 500 mA/1,000 mA (switchable)
K6EL-100
K6EL-A100
100 mA/200 mA
(switchable)
30 mA (fixed)
50 mA/150 mA (switchable)
---
---
OTG-CN52
OTG-CN77
OTG-CN112
---
Medium-sensitivity models
Model
K6EL-200
K6EL-A200
Indoor separate-type models
200 mA/500 mA
(switchable)
---
---
52 mm
77 mm
112 mm
---
Diameter of through-hole
CSM_K6EL_DS_E_3_1
K6EL-500
K6EL-A500
500 mA/1,000 mA
(switchable)
1

Related parts for Y92F-71

Y92F-71 Summary of contents

Page 1

Ground Fault Relay K6EL Economical, Compact, High-performance, DIN 48 × 48-mm Ground Fault Relay for Low Voltages • Performs continuous monitoring and detection of ground faults in low-voltage circuits due to the deterioration of insulation in electrical devices. • Higher ...

Page 2

... Note: 1. “OK” indicates groupings that can be combined freely. 2. Combinations with the OTG-LA@@ are also possible. ■ Options Flush Mounting Adapters Model Y92F-30 Y92F-71 Specifications ■ Ground Fault Relay Ratings Type Item Control power supply 100/110 VAC or 200/220 VAC, 50/60 Hz (same for all) ...

Page 3

Ground Fault Relay Characteristics Item Type High-speed models Operating time Less than 0.1 s Inertial non-operating --- time Control power supply 80% to 110% of the control power supply voltage range − °C (with no icing) Operating ...

Page 4

Internal Block Diagram 3 Input Operating From OTG ZCT protection value setting circuit circuit 4 Sensitivity selection switch (not provided on the K6EL-30) Nomenclature Power supply indicator (green) Test button (red) Sensitivity selection switch (not provided on the K6EL-30) Connections ...

Page 5

Connection Examples Installation on the Electrical Path Molded case ZCT circuit-breaker Transformer kt lt OTG ZCT l k Auxiliary relay Y Alarm buzzer K6EL 1 11 Ground Fault Relay 100/110 ...

Page 6

... R0.5 max Note: Recommended panel thickness 3.2 mm. Mounting Hole P3GA-11 Cutout Dimensions Back Connecting Socket R0.5 max Note: Recommended panel thickness 3.2 mm. 91.4 Note: The same dimensions apply when using the Y92F-71 Adapter. Mounting Holes Two, 4.5-dia. holes 40± 0 ...

Page 7

PL11 Back Connecting Socket 51 max max. Front Cover Model Y92A-48B (Hard Cover) Y92A-48D (Soft Cover) ZCT Indoor Through-type Models OTG-L21 ( OTG-L30 (100 A) OTG-L42 (200 A) 109 OTG-L68 (400 ...

Page 8

OTG-L82 (600 A) 158 OTG-L156 (1,000 A) 263 9 Indoor Separate-type Models OTG-CN52 (200 A) 141 9.3 6.2 138 17 82 dia. 160 (mounting pitch) 28 172 33 156 dia. L 138 230 60 3.2 270 ...

Page 9

OTG-CN77 (400 A) 157 70 53 OTG-CN112 (600 A) 200 107 70 53 ■ Maximum Wire Sizes for ZCTs Wire/cable Model Rated Through-hole current diameter OTG-L21 dia. OTG-L30 100 A 30 dia. OTG-L42 200 A 42 dia. ...

Page 10

Test Circuit 100 VAC Switch Slidac mA Ammeter OTC R Select the resistance R shown in the test circuit diagram according to the K6EL’s rated sensed current. Change the current using the slidac and ascertain the ...

Page 11

Q&A Q: How does the K6EL operate when used for inverter loads (e.g., inverter motors and inverter air conditioners)? A: The influence of high-frequency noise generated by the inverter has been reduced by combining a special ground fault relay IC ...

Page 12

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...

Related keywords