PDSM362 TIMEGUARD, PDSM362 Datasheet - Page 3

no-image

PDSM362

Manufacturer Part Number
PDSM362
Description
PRSNCE DTCTR, PIR, SM, 2000W, 2 CH
Manufacturer
TIMEGUARD
Datasheet

Specifications of PDSM362

Beam Angle
360°
Base Type
Incandescent / Halogen
External Depth
121.5mm
External Length / Height
42.5mm
External Width
121.5mm
Ip/nema Rating
IP40
Power Rating
2000W
Sensing Distance Max
7m
Svhc
No SVHC (15-Dec-2010)
Lamp Base Type
Incandescent / Halogen
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3.3.2 (cont). The protection covers have teeth (see Fig. 8-A) giving a
degree of cable clamping if power and load are connected by individual
wires (0.8 -1.8mm dia.).
If connection is by cable (9 - 11mm dia.) then use of a coarse rat-tailed
file to open out as many of the holes as necessary using the markings
on the inside of the protection cover as an approximate guide
(see Fig. 8-B).
Referring it to the appropriate wiring diagram insert the wires into the
correct screw terminals and tighten fully. Then plug the sensor lead into
SENSOR A socket only.
Use the coarse rat-tailed file to open a single hole (smaller than that
above) in the remaining protection cover to take the sensor cable with a
degree of strain relief. Secure down the protection covers.
3.3.3 Feed the wires/cables followed by the power unit through the
65mm dia. ceiling hole (see Fig. 9).
3.3.4 Force the spring clips back until they can feed into the ceiling hole
(see Fig. 10-A) and then push the sensor upwards into place so that its
flange fits tightly against the ceiling (see Fig. 10-B).
Fig. 10-A
Fig. 10-B
Fig. 8-A
Fig. 8-B
Fig. 9
4
4.1 Time, LUX and Meter Controls
Following marked values (excepting TEST and
the values are continuously adjustable over the control range
(see Fig.11-A & Fig.11-B).
4.1.1 TIME control adjustment
These are delay times between the sensor being triggered and the
controller switching off assuming no further detections are made.
If there are additional detections the time delay applies from the latest
detection.
PDFM362:
TIME 1: Adjustable from 5sec to 20min (lighting). (Extendable to 30min
and 60min when in use with the IR-10 remote controller).
TIME 2: Adjustable from 10sec to 60min (HVAC).
PDFM361:
TIME: Adjustable from 5sec to 20min (lighting). (Extendable to 30min
and 60min when in use with the IR-10 remote controller).
4.1.2 LUX control adjustment
The LUX level below which the sensor will operate is adjustable from
10 LUX (operation only after dusk) to 2000 LUX (operation at any light
level).
4.1.3 METER control adjustment
This control sets the diameter of detection coverage at floor level.
Assuming a ceiling height of 2.5m at the + end of the scale the
coverage diameter will be 7m, at the - end of the scale the coverage
diameter will be 1m.
The affect of METER control at other ceiling heights is shown in section 3.1.
4.2 Test Mode
4.2.1 Sensor warm up
The detector will take a minimum of 60 seconds to warm up when the
power is connected to it for the first time or if the power is being
re-connected after being turned off.
During this period load I and the sensor LED will both be on. After the
warm up is finished the sensor will revert to operation according to the
settings of the controls on the sensor body.
4.2.2 LED function
There is a red LED (see Fig. 12) built into the sensor and visable through
the PIR lens that shows the status of the loads and enables testing to be
carried out without the loads
being connected.
If the IR-10 remote controller
is in use the LED will flash to
give confirmation of the
commands and adjustments
made by the IR-10.
Test and Operation
Fig. 11-A (PDFM362 control dials)
Fig. 11-B (PDFM361 control dials)
Fig. 12
) are approximate,