6470 KIT-300FT AEMC, 6470 KIT-300FT Datasheet

RESISTANCE TEST KIT, 2/4 WIRE, 99.99KOHM

6470 KIT-300FT

Manufacturer Part Number
6470 KIT-300FT
Description
RESISTANCE TEST KIT, 2/4 WIRE, 99.99KOHM
Manufacturer
AEMC
Datasheet

Specifications of 6470 KIT-300FT

Wire Connection
2-Wire, 4-Wire
Resistance Measuring Range
2-point 0.01 To 99.9 Kohms
4-point 0.001 To 99.99 Kohms
Resolution (ohm)
Test Current
250mA
Lead Free Status / RoHS Status
na
Multi-Function Ground
resistance soil
resistiVitY tester
Model 6470-B
2- and 4-Wire Bond Resistance/Continuity Measurement (DC Resistance) with automatic polarity reversal
3-Pole (3-Point) Fall-of-Potential measurement with manual or automatic frequency selection
4-Pole (4-Point) Fall-of-Potential measurement for very low resistance measurements with manual or
automatic frequency selection and automatic lead compensation
4-Pole (4-Point) Soil Resistivity measurement with automatic calculation of Rho (r) and user selection of
the Wenner or Schlumberger test method
3-Pole (3-Point) Earth Coupling measurement
Manual and automatic frequency scan from 40 to 513Hz for optimum test accuracy in electrically
noisy environments
Selectable test voltage of 16 or 32V up to 250mA of test current
Auto-off power management
Automatic recognition of all electrode connections and their resistance value
Stores up to 512 complete test results in internal memory
Optically isolated USB communication
Remote set up and operation of all measurements using DataView
Automatic report generation
Rechargeable NiMH batteries from wall charger or vehicle power
Rugged dustproof and rainproof field case – IP54 rated in closed positione
Grounding standards IEC 61557 parts 4 and 5 compliant
Includes DataView
and system configuration
®
software for data storage, real-time display, analysis, report generation
®
software supplied

6470 KIT-300FT Summary of contents

Page 1

... Fall-of-Potential measurement for very low resistance measurements with manual or automatic frequency selection and automatic lead compensation ► 4-Pole (4-Point) Soil Resistivity measurement with automatic calculation of Rho (r) and user selection of the Wenner or Schlumberger test method ► 3-Pole (3-Point) Earth Coupling measurement ► ...

Page 2

... IEC standards. The adjustable test frequency provides for rejection of high levels of interference, allowing used under difficult conditions such as high stray currents that normally affect accuracy. 2 www.aemc.com ► 2- and 4-Wire Bond Resistance/Continuity Measurement (DC Resistance) with automatic polarity reversal ► ...

Page 3

... EN 61010-1 50V Cat IV, Pollution Degree 2 6470-B 0.01Ω to 100Ω 250mA Yes 0.01 to 100Ω (+, — or auto polarity) 512 test results , 1.9A output vehicle power dc dc Per EN 61557 Per EN 61557 Per EN 61557 3kV 50/60Hz 7.5 lbs (3.5kg) Polypropylene Yes Yes www.aemc.com 3 ...

Page 4

... The Schlumberger test displays test lead connection, soil resistivity test results ( and electrode spacing. 4 www.aemc.com 3-Point Fall-of-Potential test The 3-Point Fall-of-Potential test displays test lead connection, grounding rod resistance and test electrode resistances. Test voltage, current or frequency can also be displayed with a button press ...

Page 5

... Z Electrode Distance ___________________________________________________ ft Test Conditions Temp: ___________ Soil: Moist Dry Soil Type Loam Sand & Gravel Shale Clay Sandstone Granite Slate 100 Electrode Distance in % from the Grounding Electrode to the Z Electrode software. ® www.aemc.com the operator’s comments and analysis. Limestone Other _____________ 100 5 ...

Page 6

... Distance for Y electrode can also be entered manually and a Fall-of-Potential plot generated. 6 www.aemc.com ® Bond test setup screen — operator can choose two or four wire test method. Soil resistivity test setup screen — operator can select either ...

Page 7

... USB communications port Rotary function selection switch Start / Stop test button Catalog #2135.04 www.aemc.com 7 ...

Page 8

... T-shaped auxiliary ground electrodes, set of five spaded lugs, one 100 ft AEMC ground tester workbook CD, carrying bag for meter, carrying bag for kit and user manual Accessories (Optional) 25Ω ...