P009KBKF HAMMOND POWER SOLUTIONS, P009KBKF Datasheet - Page 4

no-image

P009KBKF

Manufacturer Part Number
P009KBKF
Description
POTTED 3PH 9kVA 480-208 CU
Manufacturer
HAMMOND POWER SOLUTIONS
Type
Distributionr
Datasheet

Specifications of P009KBKF

Brand/series
Titan Series
Configuration
NEMA/Encapsulated
Depth
9.50
Dimensions
16.63"W×17.89"H×10.25"D
Frequency
60 Hz
Height
17.89
Mounting Type
Wall
Number Of Outlets
2
Number Of Outputs
2
Phase
3 Delta
Power, Rating
9000 VA
Primary Type
Transformer
Standards
cULus
Termination
Leadwires
Voltage, Primary
480 VAC
Voltage, Secondary
120/208 VAC
Weight
211 lbs.
Width
15.91
SECTION 9
HPS TITAN
ENVIRONMENTS AND HAZARDOUS LOCATIONS
THREE PHASE STANDARD SPECIFICATIONS
.
Other voltages not listed in this section are available upon request. Please contact customer service for
details, price and availability.
All HPS TITAN three phase transformers are UL Listed for “Class 1, Division 2, Groups A, B, C and D Hazardous
Locations” and are ABS Type Approved for “Marine Duty Service and Offshore Applications - Electrical Distribution
and Propulsion”. And with a North American Temperature Classification of T3C, the HPS TITAN series will remain
cool under load.
© Hammond Power Solutions Inc.
UL 1604, Class I, Division 2
ABS Type Approval
Frequency
Insulation System
Electrostatic Shield
Encapsulation
Enclosure Type
Enclosure Finish
Termination
Conduit Knock-Outs
Impedance
Mounting
Sound Level
F
or termination details see page
269.
File: E258346
Certificate No.: 04-MO523208-X
60 Hz
130°C (80°C rise) standard on all units
Standard on all units.
All units are encapsulated with electrical
Heavy Duty Encapsulated NEMA Type 3R
Optional NEMA 4, 4X (stainless steel) and 12
ANSI 61 Grey, UL50
Top accessible separate high and
low voltage lead wires or copper tabs.
Standard side and rear knock-outs on all units.
Typically 1 to 5%.
Standard Wall Mounting.
Meets NEMA ST-20 standards.
(optional low noise units available on request)
SERIES TRANSFORMERS FOR HARSH
grade silica sand and resin compounds.
(50/60 Hz on units with 380V primary)
2 kVA to 5 kVA
228
SERIES TRANSFORMERS
File: E258346
Certificate No.: 04-MO523208-X
60 Hz
180°C (115°C rise) standard on all units.
Optional 130°C (80°C rise) available.
Standard on all units.
All units are encapsulated with electrical
Heavy Duty Encapsulated NEMA Type 3R
Optional NEMA 4, 4X (stainless steel) and 12
ANSI 61 Grey, UL50
Top accessible separate high and
low voltage lead wires or copper tabs.
Standard side and rear knock-outs on all units.
Typically 1 to 5%.
Standard Wall Mounting up to 15 kVA.
(
45 kVa.)
Lifting provisions standard 6 kVA to 150 kVA.
Meets NEMA ST-20 standards.
(optional low noise units available on request)
grade silica sand and resin compounds.
Optional wall mounting kit available for 30 kVA and
(50/60 Hz on units with 380V primary)
Floor Mount only over 45 kVA.
HPS TITAN
F
Data subject to change without notice.
6 to 150 kVA
or accessories see pages
254-257.

Related parts for P009KBKF