NP24-12BFR EnerSys, NP24-12BFR Datasheet - Page 6

no-image

NP24-12BFR

Manufacturer Part Number
NP24-12BFR
Description
LEAD ACID BATTERY, 12V, 24AH
Manufacturer
EnerSys
Datasheets

Specifications of NP24-12BFR

Battery Capacity
24Ah
Battery Voltage
12V
Battery Technology
Lead Acid
External Height
125mm
External Width
175mm
External Depth
166mm
Weight
20lb
Battery Terminals
Bolt
Height
4.92"
Width
6.54"
Brand/series
NP Series
Capacity
24000 mAh
Chemical System
Lead Acid
Dimensions
166mmL×175mmW×125mmH
Primary Type
Rechargeable
Resistance, Internal
9.5 Milliohms
Size
Rectangular
Temperature, Operating
-15 to +50 °C
Temperature, Operating, Maximum
+50 °C (Charge), +60 °C (Discharge)
Temperature, Operating, Minimum
-15 °C (Charge), -20 °C (Discharge)
Termination
Bolt Fastened
Voltage, Nominal
12 V
Voltage, Rating
12 V
Lead Free Status / RoHS Status
na
Lead Free Status / RoHS Status
na
6
www.enersys.com
Charging
Discharge
Storage
• LAYOUT
• TERMINAL
Range Summary
Standby use: Apply constant voltage charging at 2.275 volts
per cell (or 2.25–2.30VPC).
Cyclic use: Apply constant voltage charging at 2.40-2.50 VPC.
Initial charging current should be set at less than 0.25CA.
Top charge: Product in storage (ambient temperature 25°C/77°F)
requires a top charge every six months. Apply constant voltage at
2.40 volts per cell, initial charging current should be set at
less than 0.1CA for 15 to 20 hours.
Stop operation when voltage has reached the minimum
permissible voltage. Recharge immediately.
Do not operate at 6CA or more current continuously.
Always store battery in a fully charged condition.
If battery is to be stored for a long period, apply a recovery
top-charge every 6 months.
Store batteries in a dry and cool location.
U Positive
Terminal
Faston tab : 187
U Negative
Terminal
6
1
A
MG Positive
0.430
Tyco. 1-480318-0 L
0.860
2
7
MG Negative
0.295
Automotive Type
0.530
AP Positive
Temperature
Incorporating battery into equipment
Others
Terminal height above cover
Terminal
Type
Keep within ambient temperatures of –15
charging and discharging.
Encase battery in a well ventilated compartment.
Avoid installing battery near heated units such as a transformer.
House the battery in the lowest section of the equipment
enclosure or rack to prevent unnecessary battery temperature
rise.
Avoid terminal short circuit.
DO NOT expose to open flame.
Avoid setting batteries in environments which can cause
direct contact to gasoline, paint thinner, organic solvents,
synthetic resins, oil, etc.
MG
NB
MJ
AP
U
B
3
8
Automotive Type
AP Negative
22.8
28.4
22.8
38.1
22.8
mm
5.1
NP33-12
0.20
0.90
1.12
0.90
1.50
0.90
ins
NP55/75/100-12
21.1
26.9
21.1
36.3
21.1
mm
3.3
0.13
0.83
1.06
0.83
1.43
0.83
ins
NB Terminal
Publication No: US-NP-AM-002 • June 2006
4
9
0
C to +50
Note:
Dimensions are in inches (mm)
Tolerances are -
and -
dimensions.
B Terminal
+
0.08 in. (-
0
C for both
+
+
2mm) for height
0.04 in. (-
MJ Terminal
5
+
1mm)
M

Related parts for NP24-12BFR