E8EB-10B Omron, E8EB-10B Datasheet - Page 6

no-image

E8EB-10B

Manufacturer Part Number
E8EB-10B
Description
PRESSURE SWITCH
Manufacturer
Omron
Series
E8EBr
Type
Gager
Datasheets

Specifications of E8EB-10B

Pressure Type
Gauge
Operating Pressure
0.15 PSI, 1 kPa
Port Size
Female, 1/8" (3.175mm) NPN
Output
1 ~ 5V
Voltage - Supply
24V
Termination Style
Cable
Operating Temperature
-10°C ~ 55°C
Package / Case
Module
Output Voltage Range
1 to 5V
Pressure Range
0 to 1000KPa
Mounting
Din-Rail
Pin Count
4
Operating Temp Range
-10C to 55C
Operating Temperature Classification
Commercial
Operating Supply Voltage (typ)
24V
Operating Supply Voltage (min)
21.6V
Operating Supply Voltage (max)
26.4V
Mounting Style
DIN Rail
Maximum Operating Temperature
+ 55 C
Minimum Operating Temperature
- 10 C
Operating Supply Voltage
24 V
Output Voltage
1 V to 5 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E8EB10B
Safety Precautions
This product is not designed or rated for ensur-
ing safety of persons.
Do not use it for such purposes.
Do not use the product in atmospheres or environments that
exceed product ratings.
Dimensions
E8EB
• If the diaphragm is damaged, the Pressure Sensor will not
• The pressure inlet has an R (PT) 1/8 taper screw and M5 fe-
• The most-suitable wrench is 17 mm in size.
• Make sure that the tightening torque of the M5 female screw
operate properly. Do not insert a screwdriver or steel wire
into the interior of the pressure-sensitive parts through the
pressure port.
male screw that conforms to JIS Standards. Apply sealing
tape around the female taper screw so that no pressure
leakage will occur.
is 9.8 N·m or less.
Mounting
Precautions for Correct Use
http://www.ia.omron.com/
WARNING
44
33.2
17
30
Rc (PT) 1/8
4.4-dia.
holes
19±0.1
Two,
Pressure Setting
3.7
• After the pressure is set with the pressure adjuster, cover
3.5
the adjuster with the rubber bushing so that no dust or any
other foreign material will penetrate into the interior of the
E8EB.
Adjustment
10.9
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
8.5
21
17.5
*
*3.8-dia. vinyl-insulated round cable with 4 conductors,
(Conductor cross-section: 0.2 mm
Standard length: 2 m
1.5
Pressure
adjuster
7 dia.
12.8 dia.
16.4
2
, Insulator diameter: 1.0 mm);
Operation
indicator (red)
5.2 x 5.2
E8EB
(Unit: mm)
6