Network Instructions
SYSMAC NET
SYSMAC LINK
Read
(@)RECV(98)
Mnemonic
Name
Symbol
RECV(98)
S
D
C
Instruction Set
Transfers data from the source words (S is
the first word) from node N of the specified
network (in a SYSMAC LINK or SYSMAC
NET System) to the destination words
starting at D. The format of the control
words varies depending on the type of
system. In both types of systems, the first
control word (C) gives the number of words
to be transferred.
For SYSMAC NET Systems, in the second
word (C+1), bit 14 specifies the system (0
for system 1, and 1 for system 0), and the
rightmost 7 bits define the network number.
The left half of word C+2 specifies the
source port (00: NSB, 01/02: NSU), and the
right half specifies the source node number.
For SYSMAC LINK Systems, the right half
of C+1 specifies the response monitoring
time (default 00: 2 s, FF: monitoring
disabled), the next digit to the left gives the
maximum number of re-transmissions (0 to
15) that the PC will attempt if no response
signal is received. Bit 13 specifies whether a
response is needed (0) or not (1), and bit 14
specifies the system number (0 for system
1, and 1 for system 0). The right half of C+2
gives the source node number.
SYSMAC LINK
C
C+1
C+2
C
C+1
C+2
SYSMAC NET
Source node N
S+n--1
S+1
n: no. of words to be transmitted (0 to 1000)
0X00
Source port no.
(NSB: 00, NSU: 01/02)
n: no. of words to be transmitted, 0 to 1000
0XX0
0000
S
Re-trans
missions
0000
0000
Function
Destination node
Response monitor time
(0.1 to 25.4 s)
Source node no.
(0 to 62)
Network no.
(0 to 127)
Source node no.
(0 to 126)
D+n--1
D+1
D
S:
IR
SR
HR
AR
TC
DM
LR
Operands
D/C:
IR
HR
AR
TC
DM
LR
CPU31
HS-CPU31
HS-CPU33
CPU