LC1D115M7 SQUARE D, LC1D115M7 Datasheet - Page 3

no-image

LC1D115M7

Manufacturer Part Number
LC1D115M7
Description
CONTACTOR 600VAC 115AMP IEC +OPTIONS
Manufacturer
SQUARE D
Datasheet
[Ui] rated insulation
voltage
Electrical durability
Power dissipation per
pole
Safety cover
Mounting support
Standards
Product certifications
Connections - terminals
Tightening torque
Operating time
Safety reliability level
Mechanical durability
Operating rate
1000 V for power circuit conforming to IEC
60947-4-1
600 V for signalling circuit certifications UL
600 V for signalling circuit certifications CSA
690 V for signalling circuit conforming to IEC
60947-1
600 V for power circuit certifications UL
600 V for power circuit certifications CSA
0.95 Mcycles 115 A AC-3 at Ue <= 440 V
0.8 Mcycles 200 A AC-1 at Ue <= 440 V
7.9 W AC-3
24 W AC-1
With
Plate
Rail
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 n°14
BV
CCC
CSA
DNV
GL
GOST
RINA
UL
LROS
Power circuit: connector 2 cable(s) 10...50 mm² - ca-
ble stiffness: solid - without cable end
Power circuit: connector 1 cable(s) 10...120 mm² -
cable stiffness: solid - without cable end
Power circuit: connector 2 cable(s) 10...50 mm² - ca-
ble stiffness: flexible - with cable end
Power circuit: connector 1 cable(s) 10...120 mm² -
cable stiffness: flexible - with cable end
Power circuit: connector 2 cable(s) 10...50 mm² - ca-
ble stiffness: flexible - without cable end
Power circuit: connector 1 cable(s) 10...120 mm² -
cable stiffness: flexible - without cable end
Control circuit: screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 1 cable(s)
1...2.5 mm² - cable stiffness: solid - without cable end
Control circuit: screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: flexible - without cable
end
Control circuit: screw clamp terminals 1 cable(s)
1...2.5 mm² - cable stiffness: flexible - without cable
end
Control circuit: screw clamp terminals 1 cable(s)
1...2.5 mm² - cable stiffness: flexible - with cable end
Control circuit: screw clamp terminals 2 cable(s)
1...2.5 mm² - cable stiffness: flexible - with cable end
Power circuit: 12 N.m - on connector hexagonal 4
mm
Control circuit: 1.2 N.m - on screw clamp terminals -
with screwdriver Philips No 2
Control circuit: 1.2 N.m - on screw clamp terminals -
with screwdriver flat Ø 6 mm
20...50 ms closing
6...20 ms opening
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
8 Mcycles
2400 cyc/h at <= 60 °C
3