85100636 Crouzet USA, 85100636 Datasheet - Page 135

no-image

85100636

Manufacturer Part Number
85100636
Description
SAFETY RLY, KZH3-RS 24VAC-VDC
Manufacturer
Crouzet USA
Series
KZH3-RSr
Datasheet

Specifications of 85100636

Contact Form
3PST (3 Form A)
Contact Rating (current)
6A
Switching Voltage
440VAC - Max
Relay Type
Safety
Coil Voltage
24VAC/DC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Coil Type
-
Coil Current
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For more information www.crouzet.com
UA1-A2
Dimensions
MCI
Connections
MCI
Principles
MCI
1
2
A1 - A2 : Power supply 110...240 VAC
A1 - A3 : Power supply 240 VAC
B
C
D
E
F
G
1
0
1
0
threshold
Relay
Amplitude of measured current
Hysteresis = Threshold - 15 %
Closed
Open
I
(+)
(-)
A2
A1
16,8
Ø 5,5
T1
U
82,2
I
43,7
A3
T2
5
R
3
T3
11
14
17,5
4,5
4
5
6
Operating principle
The relay contact (11 and 14) closes if the current is greater than the threshold.
The relay contact (11 and 14) opens if the current is less than 15 % (hysteresis) of the threshold.
Note :
Delay on pick-up (T1) 500 ms maximum. Response time to sensing (T2) 400 ms ± 50 %.
Response time to turn-off (T3) 120 ms ± 50 %.
The graduated set-point scale on the front relates to sinusoidal or delta current measurement. The
MCI can measure non-sinusoidal currents, for example currents subject to phase control. In this
case, the display may be affected by an error coefficient which is a function of the tripping angle of
the phase controller (form factor).